6 Operating and display elements

1

3

6

2

5

4

Ι  ΙΙ

Ι  ΙΙ

1: LED yellow

Indication of the switching status output 1 / output 2;
lights when the corresponding output is switched / the relay is en-
ergised.

2: LED red

Fault indication for input circuit 1 / input circuit 2;
lights in case of wire break or short circuit in the respective input
circuit. The corresponding output is not active (transistor blocked,
relay de-energised).

3: LED green

Lights when supply voltage is applied.

4: Selector switch S1 Programming the output function

S1 / S2 = 1: direct operation (output switches like input signal: IN =
ON 

 OUT = ON).

S1 / S2 = 2: inverted operation (output switches opposed to the in-
put signal: (IN = ON 

 OUT = OFF).

For single-channel units S2 has no function.

5: Selector switch S2

GB

Summary of Contents for N0030A

Page 1: ...Operating instructions Switching amplifiers N0030A N0031A N0032A N0033A N0034A 80299361 00 02 2021 GB...

Page 2: ...3 2 ATEX certificate 4 3 3 IECEx certificate 4 3 4 Identification 4 4 Installation 4 4 1 Requirements for cables and connection cables 5 4 2 Requirements in case of use as associated equipment 5 5 Ele...

Page 3: ...the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Intended use If the operating instructions or the technical data are...

Page 4: ...ategory 1G 2G apparatus for gas atmosphere The requirements of the standards EN IEC 60079 0 2018 EN 60079 11 2012 EN 60079 26 2007 Corr 2009 are met II 1 D group II category 1D apparatus for dust atmo...

Page 5: ...ed u Make sure the insulation of the conductor reaches all the way to the connecting terminal u The tightening torque for the screws of the connecting terminal must be adhered to If the voltage exceed...

Page 6: ...IEC EN 60079 25 must be observed proof of intrinsic safety 5 Electrical connection NAMUR switch Mechanical switch Input circuit no 1 2 3 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 10 k 10 k 400 R 2 k 1 2 3 4...

Page 7: ...wire break or short circuit in the respective input circuit The corresponding output is not active transistor blocked relay de energised 3 LED green Lights when supply voltage is applied 4 Selector s...

Page 8: ...no 1 S3 must be in position I Without short circuit monitoring for input circuit no 2 and S3 in position I Without short circuit and wire monitoring for input circuit no 3 and S3 in position II 7 Mai...