background image

6

u

If intrinsically safe units are connected to the intrinsically safe circuits of the
corresponding equipment, the respective upper limiting values consistent with
the explosion protection according to IEC/EN 60079-14 or IEC/EN 60079-25
must be observed (proof of intrinsic safety).

5 Electrical connection

NAMUR switch

Mechanical switch

Input circuit no.

1

2

3

1 2 3

4 5 6

1 2 3

4 5 6

1 2 3

4 5 6

10 kΩ

10 kΩ

400 Ω ≤ R ≤ 2 kΩ

1 2 3

4 5 6

Maximum permissible values of the control circuits in type of protection intrinsic
safety

Voltage

10.6 V

current

19.1 mA

Power

51 mW

External inductance

97 mH (IIC) / 390 mH (IIB)

External capacitance

2.32 µF (IIC) / 16.2 µF (IIB)

Summary of Contents for N0030A

Page 1: ...Operating instructions Switching amplifiers N0030A N0031A N0032A N0033A N0034A 80299361 00 02 2021 GB...

Page 2: ...3 2 ATEX certificate 4 3 3 IECEx certificate 4 3 4 Identification 4 4 Installation 4 4 1 Requirements for cables and connection cables 5 4 2 Requirements in case of use as associated equipment 5 5 Ele...

Page 3: ...the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Intended use If the operating instructions or the technical data are...

Page 4: ...ategory 1G 2G apparatus for gas atmosphere The requirements of the standards EN IEC 60079 0 2018 EN 60079 11 2012 EN 60079 26 2007 Corr 2009 are met II 1 D group II category 1D apparatus for dust atmo...

Page 5: ...ed u Make sure the insulation of the conductor reaches all the way to the connecting terminal u The tightening torque for the screws of the connecting terminal must be adhered to If the voltage exceed...

Page 6: ...IEC EN 60079 25 must be observed proof of intrinsic safety 5 Electrical connection NAMUR switch Mechanical switch Input circuit no 1 2 3 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 10 k 10 k 400 R 2 k 1 2 3 4...

Page 7: ...wire break or short circuit in the respective input circuit The corresponding output is not active transistor blocked relay de energised 3 LED green Lights when supply voltage is applied 4 Selector s...

Page 8: ...no 1 S3 must be in position I Without short circuit monitoring for input circuit no 2 and S3 in position I Without short circuit and wire monitoring for input circuit no 3 and S3 in position II 7 Mai...