8.8.3 Fault during the teach operation
The teach operation is cancelled in case of a fault:
> LEDs are flashing green/yellow with 8 Hz�
> The unit returns to the operating mode with unchanged settings�
Possible faults:
• Time error (teach time too long / too short)
• Internal sensor signal not clear
• Wrong output function:
(→ 8.8 Parameter setting via the teach input)
• Process value too low (< 9 %, e�g� for powders), SPx/rPx must be set manually
(→ 8.1 Parameter setting via PC and IO-Link interface)
�
9 Operation
When the supply voltage has been applied, the unit is in the operating mode�
It carries out its evaluation functions and switches the outputs�
Outputs OUT1 and OUT2 complement each other�
The following table shows the factory settings� In this state OUT1 = Hno
and OUT2 = Hnc�
►
Check whether the unit operates correctly�
9.1 Switching states and display by LEDs
Operating status
LEDs
OUT1
OUT2
Unit ready for operation,
no medium detected
green
OFF
ON
Unit ready for operation, medium detected
yellow
ON
OFF
No operating voltage
OFF
OFF
OFF
Short circuit output 1
flashing yellow
-
1)
Short circuit output 2
flashing yellow
1)
-
Error / failure
-
OFF
OFF
Teach operation
Fault during the teach operation
LEDs are flashing green/yellow with 8 Hz
1
) according to the level
The LEDs always indicate the switching status of output OUT1
(exception: Teach mode
)�