Binary level sensor for overflow prevention / leakage detection according to WHG
LI213x
17
u
Fill the collection system or simulate the full state in a suitable
way with a test tank filled with a test medium until the active zone
is completely covered.
u
Unlock device
u
Actuate the teach button for at least 4 s / not more than 7 s.
w
First, the green LED3 is shortly extinguished, after 1 s the two
yellow LEDs start flashing slowly (approx. 1 Hz) before flashing
quickly (approx. 2 Hz) after 4 s.
u
Release the teach button (remove metal object).
w
Successful full adjustment is acknowledged with a double-
flashing (approx. 2 Hz) of the green LED.
w
The device is ready for operation.
After the full adjustment, both yellow LEDs are off, only the green LED is still on.
7.6 Parameter setting via IO-Link
After a factory reset the device reboots and the factory settings are restored.
When the medium is changed, it may also be necessary to adapt the device settings.
Parameters can be set before installation or during operation.
If you change parameters during operation, this will influence the function of the plant.
u
Ensure that there will be no malfunctions in your plant.
During parameter setting the unit remains in the operating mode. It continues to monitor with the
existing parameter until the parameter setting has been completed.
Requirements for parameter setting via the IO-Link interface:
ü
A suitable parameter setting software, e.g. ifm moneo|configure
ü
The Input Output Device Description (IODD) for the device, see
ü
One IO-Link master
u
Connect the IO-Link master to a parameter setting software.
u
Set the port of the master to the IO-Link operating mode.
u
Connect the device to a free port of the IO-Link master.
w
The unit switches to IO-Link mode.
u
Change parameter settings in the software.
u
Write parameter settings to the unit.
Notes on parameter setting
Ò
Manual of the parameter setting software