IO-Link Master with PROFINET Interface StandardLine 8 Ports IP 65 / IP 66 / IP 67 
 

12 

Mounting 

Content 

Mount the device ....................................................................................................................................12 

34058 

 

5.1 

Mount the device 

34059 

 

►  Disconnect the system from power before installation. 
►  For installation choose a flat mounting surface. 
►  Please observe the maximum tightening torque. 

  

►  Fix the unit to the mounting surface using 2 M5 mounting screws and washers. 

 

Tightening torque: 1.8 Nm 

►  Ground the unit via the two mounting screws of the upper mounting lugs. 

Summary of Contents for IO-Link master-PROFINET AL1102

Page 1: ...80280033 00 11 2018 Operating Instructions IO Link Master with PROFINET Interface StandardLine 8 Ports IP 65 IP 66 IP 67 AL1102 Firmware 2 2 x or higher LR DEVICE 1 4 0 x or higher English...

Page 2: ...4 Function 9 4 1 Communication parameter setting evaluation 10 4 1 1 IO Link 10 4 1 2 PROFINET 10 4 1 3 Parameter setting 10 4 1 4 Visual indication 10 4 2 Digital inputs 11 4 3 IO Link supply 11 5 Mo...

Page 3: ...INET 33 9 2 1 Install GSD Files 34 9 2 2 Integrate the IO Link master in the project 35 9 2 3 Configure the IO Link master 35 9 2 4 Configure IO Link ports 36 9 2 5 Configure IO Link devices 37 9 2 6...

Page 4: ...IO Link Master with PROFINET Interface StandardLine 8 Ports IP 65 IP 66 IP 67 4...

Page 5: ...r Association USA www odva org EtherNet IP is the property of the ODVA EtherCAT is a registered trade mark and patented technology licensed by Beckhoff Automation GmbH Germany IO Link www io link com...

Page 6: ...NOTICE Property damage is to be expected or may result Important note Non compliance can result in malfunction or interference Information Supplementary note Request for action Reaction result see abc...

Page 7: ...e operating instructions Adhere to the warning notes on the product 2 2 Required background knowledge 34185 This document is intended for specialists Specialists are people who based on their relevant...

Page 8: ...use 8 34079 3 1 Permitted use 34209 The IO Link master serves as a gateway between intelligent IO Link devices and the PROFINET network The device is designed for use without a control cabinet in the...

Page 9: ...IO Link Master with PROFINET Interface StandardLine 8 Ports IP 65 IP 66 IP 67 9 4 Function Content Communication parameter setting evaluation 10 Digital inputs 11 IO Link supply 11 33836...

Page 10: ...nk devices and the higher level PROFINET controller Supported protocols SNMP LLDP MRP DCP RTA RTC Class 1 nicht synchronisiert PROFINET features FSU I M0 4 read write Device description GSDML file 4 1...

Page 11: ...k ports X01 X08 All inputs refer to the potential of the device supply pin 3 4 3 IO Link supply 34077 The device has 8 supplies for IO Link devices The IO Link ports X01 X08 are ports class A Every su...

Page 12: ...the device 34059 Disconnect the system from power before installation For installation choose a flat mounting surface Please observe the maximum tightening torque Fix the unit to the mounting surface...

Page 13: ...ions to avoid excessive strain on the installation points and the M12 connections Ensure correct fit and proper assembly of the M12 connecting parts If these instructions are not complied with the spe...

Page 14: ...0 8 Nm Connect the unit via the M12 socket X21 and or X22 to the industrial Ethernet network e g laptop PC with installed parameter setting software LR DEVICE laptop PC with installed monitoring softw...

Page 15: ...ass A operation 51959 Wiring information The connected IO Link devices must be supplied exclusively via the IO Link master The additional digital inputs IO Link ports X01 X08 pin 2 have a type 2 behav...

Page 16: ...ssuring basic insulation according to IEC 61010 1 secondary circuit with 30 V DC maximum supplied from mains circuit up to 300 V of overvoltage category II Ensure that the IO Link devices and the conn...

Page 17: ...g to EN61010 1 secondary circuit with maximum 30 V DC supplied by mains circuit up to 300 V of overvoltage category II Tightening torque 0 6 0 8 Nm Maximum cable length 25 m To connect the device use...

Page 18: ...rview 18 LED indicators 19 34063 7 1 Overview 34612 Status LEDs RDY BF and SF Status LEDs S 19 Status LEDs LNK and ACT of the PROFINET ports 1 X21 and 2 X22 Ethernet interface S 19 Status LED US of th...

Page 19: ...shes 5 Hz Firmware update off Gateway does not function Unit reboots BF red on Bus error flashes 1 Hz No connection to the PROFINET controller off error free SF red on Error in gateway At least 1 IO L...

Page 20: ...k ports Class A 34074 Each IO Link port Class A has 2 LEDs marked as IOL and DI The LEDs indicate the status of the IO Link port Status LED Description IOL yellow off Port configured as DI DO pin 4 C...

Page 21: ...display elements S 18 To enable parameter setting of the AL1102 the fieldbusinterface of the network environment must be configured correspondingly Configure the fieldbus interface ports X21 X22 Fiel...

Page 22: ...Cycle time Vendor ID ID of the manufacturer of the IO Link device Device ID ID of the IO Link device Name Article number of the IO Link device For ifm articles This article number is stored along with...

Page 23: ...IO Link Master with PROFINET Interface StandardLine 8 Ports IP 65 IP 66 IP 67 23 9 Configuration Content LR DEVICE 24 PROFINET 33 33858...

Page 24: ...27 IO Link ports Activate data transfer to the LR SMARTOBSERVER 28 IO Link ports Configure operating mode 29 IO Link ports Set the device validation and data storage 30 Firmware Reset device to facto...

Page 25: ...the connected IO Link devices without being connected to the AL1102 OFFLINE mode The configuration created in this way can be stored as a file lrp and loaded to the AL1102 and activated at a later dat...

Page 26: ...ROFINET and IoT Core have read access rights to events alarms PROFINET IoT read only PROFINET has read and write access rights to parameters and process data PROFINET has read access rights to events...

Page 27: ...0 2147483647 500 ms 2147483647 ms Application Tag Source identifier of the IO Link master in the structure of the LR SMARTOBSERVER String32 Factory setting AL1102 After changing the parameter Port LR...

Page 28: ...ta the interfaces to the LR SMARTOBSERVER have to be correctly configured IoT Configure the interface to the LR SMARTOBSERVER S 27 To activate deactivate data transfer Select Port x menu x 1 8 The men...

Page 29: ...es Mode Operating mode of the IO Link port Disabled Port deactivated DI Operation as digital input DO Operation as digital output IO Link Operation as IO Link interface Cycle time actual Current cycle...

Page 30: ...r it is an IO Link device of the same type validation via vendor ID and device ID No data storage Type compatible V1 1 device with Backup Restore IO Link device is compatible with the V1 1 IO Link sta...

Page 31: ...evice to factory settings Select Firmware menu The menu page shows the current settings Click on Factory Reset to reset the device LR DEVICE sets the device to the factory settings 9 1 9 Firmware Rebo...

Page 32: ...igure access rights S 26 1 Select IO Link master Start LR DEVICE Update IODD file library OR Import IODD file of the IO Link device manually Scan network for devices LR DEVICE detects IO Link master 2...

Page 33: ...nk devices 37 Read and write cyclic process data 38 Read I M datasets 39 Detect diagnostics and alarms 39 34541 On the field bus side the device can be configured with the following options PROFINET p...

Page 34: ...e The user can download the GSD file from the ifm website www ifm com To add the IO Link master to the hardware catalogue of the PROFINET projection software Download the GSD file of the AL1102 from t...

Page 35: ...1 of the IO Link master Save the project The IO Link master is integrated in the project and can be configured 9 2 3 Configure the IO Link master 52480 You can access the configuration of the IO Link...

Page 36: ...dation data storage cycle time events The following table shows the available parameters depending on the selected operating mode Operating mode of the IO Link ports Available parameters Fail safe mod...

Page 37: ...he IO Link Devices The following options are available Symbol function block Description Notes IO_LINK_DEVICE FB5001 Acyclic access to the parameters of an IO Link device Input parameter CAP Access po...

Page 38: ...NET controller Create a symbolic name and select the data type Assign an IEC address to the symbolic name Save the project Using the symbolic name the user can read the inputs and write the outputs fr...

Page 39: ...Symbol function block Description Notes GET_IM_DATA Function block for reading the I M datasets of a device GET_IM_DATA only supports the reading of the I M0 dataset Input parameters IM_TYPE 0 RDREC F...

Page 40: ...are update 41 Replace IO Link device 42 51990 The operation of the unit is maintenance free Dispose of the unit in an environmentally friendly way in accordance with the applicable national regulation...

Page 41: ...ll a new firmware version on the device Requirements File with new firmware has been downloaded Ethernet connection between laptop PC and device is established 1 Call up web interface Start web browse...

Page 42: ...orts IO Link standard 1 1 or higher 1 Set data storage Set the following parameters of the IO Link port Validation and Data Storage Type compatible V1 1 device with Restore Save changes 2 Replace IO L...

Page 43: ...orts IP 65 IP 66 IP 67 43 11 Factory settings 34594 In the factory settings the device has the following parameter settings Parameters Factory setting IP address 0 0 0 0 Subnet mask 0 0 0 0 IP gateway...

Page 44: ...IO Link Master with PROFINET Interface StandardLine 8 Ports IP 65 IP 66 IP 67 44 12 Accessories 33870 List of accessories of AL1102 www ifm com Product page Accessories...

Page 45: ...IO Link Master with PROFINET Interface StandardLine 8 Ports IP 65 IP 66 IP 67 45 13 Appendix Content Technical data 46 PROFINET 50 33879...

Page 46: ...1 Application 33878 Application Application I O modules for field applications Daisy chain function Communication interface 13 1 2 Electrical data 33808 Electrical data Operating voltage V 20 30 DC US...

Page 47: ...Link Port Class A 8 x 1 Max current load per output mA 200 Short circuit protection yes 13 1 6 Interfaces 34586 Interfaces Communication interface Ethernet IO Link Communication interface IO Link TCP...

Page 48: ...t temperature C 25 60 Storage temperature C 25 85 Max perm relative air humidity 90 Max height above sea level m 2000 Protection rating IP 65 IP 66 IP 67 Pollution Degree 2 13 1 8 Approvals tests 3387...

Page 49: ...Electrical connection 34608 Voltage supply IN X31 Connector M12 Wiring 1 24 V DC US 2 3 GND US 4 Ethernet IN OUT X21 X22 Connector M12 Wiring 1 TX 2 RX 3 TX 4 RX 5 Process connection IO Link Ports Cla...

Page 50: ...access rights to the parameter data process data and events diagnostic messages of the IO Link master and the connected IO Link devices PROFINET IoT PROFINET and LR DEVICE have read and write access...

Page 51: ...e AL1102 when a new IO Link device is connected to the IO Link port no check and clear no verification of the vendor ID and device ID no data storage Type compatible V1 0 device IO Link device is comp...

Page 52: ...eter values stored in the IO Link master are restored automatically on the IO Link device Vendor ID VID ID of the manufacturer that is to be validated 0 65535 ID of the manufacturer of the IO Link dev...

Page 53: ...O PQI 1 byte input and output data and PQI IO Link 1I 15O PQI 1 byte input and 15 bytes output data and PQI IO Link 32I PQI 32 bytes input data and PQI IO Link 16I PQI 16 bytes input data and PQI IO L...

Page 54: ...l status of the digital input on pin 4 DI FALSE OFF TRUE ON DI2 Signal status of the digital input on pin 2 if used FALSE OFF TRUE ON DA Device Available shows if the IO Link device has been recognise...

Page 55: ...or T r 1 Software Revision Software revision numbers separated by blanks e g x y z in Vx y z r 3 Revision Counter Revision counter is incremented with each parameter change r 2 Profile ID ID of sub mo...

Page 56: ...ber of the device numbers separated by blanks r 16 Hardware revision Hardware revision of the device r 2 Software revision prefix Prefix of the software revision of the device V R P U or T r 1 SOFTWAR...

Page 57: ...the IO Link master Diagnostics 0x28 EVNT_CODE_DSREADY_NOACTION Data storage completed but no action since CRC was correct Alarm 0x29 DS_FAULT_IDENT Sensor does not match the content of the data memory...

Page 58: ...the IO Link master in the project 35 Intended use 8 Interfaces 47 IO Link 10 IO Link ports 15 Activate data transfer to the LR SMARTOBSERVER 28 Configure operating mode 29 Set the device validation an...

Page 59: ...IO Link Master with PROFINET Interface StandardLine 8 Ports IP 65 IP 66 IP 67 59 T Tampering with the unit 7 Technical data 46 V Visual indication 10 Voltage supply 20 VPN connection 25...

Reviews: