EIO104
Converter IO-Link sensor ‒ 4…20 mA
6
4 Function
The device converts IO-Link process values into max. 2 analogue signals of 4…20 mA.
3
OUT1 (Analog; 4...20 mA)
OUT2 (Analog; 4...20 mA)
2
1
Fig. 1: Application example
1:
IO-Link sensor
2:
Converter IO-Link sensor ‒ 4…20 mA
3:
Analogue evaluation
4.1 Analogue output
The measuring range can be scaled via the parameters [ASP] and [AEP]:
•
[ASP] determines at which measured value the output signal is 4 mA
•
[AEP] determines at which measured value the output signal is 20 mA
[ASP] must have a lower value than [AEP].
u
Observe the minimum distance between [ASP] and [AEP]
Ò
Operating instructions sensor.
If the measured value is outside the measuring range or in the event of an internal error, the current
signal indicated in the following figure is provided.
2
1
100 %
0 %
4
3,8
3,5
FOU=OFF
20
20,5
21,5
[mA]
FOU=On
6
cr.UL UL
OL cr.OL
3
4
5
ASP
ASP*
AEP
AEP*
Fig. 2: Characteristics of the analogue output according to the standard IEC 60947-5-2
1:
Analogue signal
4:
Display range
2:
Process value
5:
Measuring range
3:
Detection zone
6:
Scaled measuring range
ASP:
Analogue start point (initial value of the measuring
range)
UL:
Below the display range
AEP:
Analogue end point (final value of the measuring
range)
cr.UL:
Below the measuring range
*
After change of factory setting
OL:
Above the display range
cr.OL:
Above the measuring range