3  Functions and features

3.1  Application area 

The unit monitors the flow of liquid and gaseous media�

3.2  Operating principle flow monitoring

•  The unit detects the flow speed to the calorimetric measuring principle and 

switches the output: 

 -output closed if medium is flowing / output open if no medium is flowing�

This applies to the unit on delivery: output = normally open� In case of need you 

can change the output to normally closed (→ 8�2)� It then applies: output open 

if medium is flowing�

•  If the flow speed increases, the switching status changes when the switch point 

is reached� 

•  If the flow speed falls again, the switching status changes if the value "SP 

minus hysteresis" is reached�

The hysteresis changes with the flow speed and it is essentially influenced by 

the set monitoring range� 

It is 2���5 cm/s for the setting 5���100 cm/s (= factory setting), it increases with 

higher flow speeds�

•  The typical response time  of the unit is 1���10 s� It can be influenced by the 

setting of the switch point:

 -Low switch point = quick reaction with rising flow�

 -High switch point = quick reaction with falling flow�

3.3  Communication (IO-Link)

•  The unit is laid out for bidirectional communication� So, the following options 

are possible:

 -Remote evaluation (transmission of the process data)�

 -Remote parameter setting (adjustment / output function)�

Device-specific parameter lists for IO-Link parameter setting are available at: 

www�ifm�com → Select your country → Data sheet direct:

Summary of Contents for efector 300 SI5010

Page 1: ...Operating instructions Flow monitors SI5010 704621 01 08 2010 UK...

Page 2: ...4 3 Mounting operation 6 5 Electrical connection 7 6 Operating and display elements 7 7 Set up and settings for water 8 7 1 Change the switch point optional 8 7 2 High flow adjustment optional 9 8 Add...

Page 3: ...n prior to set up of the unit Ensure that the product is suitable for your application without any restrictions The unit conforms to the relevant regulations and EC directives Improper or non intended...

Page 4: ...ng status changes if the value SP minus hysteresis is reached The hysteresis changes with the flow speed and it is essentially influenced by the set monitoring range It is 2 5 cm s for the setting 5 1...

Page 5: ...lation location General The sensor tip is to be completely surrounded by the medium Insertion depth of the sensor minimum 12 mm Recommended For horizontal pipes mounting from the side For vertical pip...

Page 6: ...rces of interference 4 3 Mounting operation Ensure that the system is free of pressure during installation Ensure that no media can leak at the mounting location during installa tion Grease the thread...

Page 7: ...4 2 1 3 4 1 3 2 Teach L L OUT1 Data OUT1 Data switching signal for flow limit value and data channel for bidirectional communication Teach input for teach signal 6 Operating and display elements 1 Ope...

Page 8: ...2 3 Your normal flow exceeds the representation range of the display LED 9 flashes Carry out high flow adjustment 6 2 You can restore the factory setting any time 8 3 7 1 Change the switch point optio...

Page 9: ...you should additionally adapt the unit to the minimum flow Note The following adjustment must only be carried out after the high flow adjust ment Let the minimum flow circulate in the installation or...

Page 10: ...adapt the unit to new flow conditions any time Apply the operating voltage for 5 10 s to Pin 2 high flow adjustment Apply the operating voltage for 10 15 s to Pin 2 low flow adjustment This adjustment...

Page 11: ...the representation range LED 0 flashes current flow far below the represen tation range Interference indicator Short circuit at the switching output The operating indicator and red LEDs light alterna...

Page 12: ...13 Technical data Application area Liquids and gases Operating voltage V 19 36 DC1 Current rating mA 250 Short circuit protection pulsed reverse polarity overload protection Voltage drop V 2 5 Curren...

Page 13: ...ating IP 67 Protection class III Shock resistance g 50 DIN IEC 68 2 27 11 ms Vibration resistance g 20 DIN IEC 68 2 6 55 2000 Hz Housing materials stainless steel 316L 1 4404 stainless steel 304 1 430...