• If the level is below SP1, output 1 switches. If SP1 is exceeded or if
there is a wire break, output 1 switches off (alarm).
• If the level exceeds SP2, the output 2 provides a signal (upper value
exceeded, submersible pump ON).
• If the level is below SP3, the output 3 provides a signal (lower value
reached, submersible pump OFF).
Pumping station
Empty the vessel /
overflow protection
with 3 switching out-
puts
(
bin
=
OFF
)
Replaces 3
float switches
Page 34
Applications
Configuration of the switching outputs 1 ... 3
maximum value exceeded
→
alarm
hysteresis function, normally closed (
Hnc
)
...
upper value exceeded
→
submersible pump ON
hysteresis function, normally open (
Hno
)
lower value reached
→
submersible pump OFF
hysteresis function, normally closed (
Hnc
)
each slightly below SPx, (to suppress wave movements) (preset)
L
SP1
1
0
OFS
OUT1
Hnc
1
0
OUT2
Hno
SP2
SP3
t
1
0
OUT3
Hnc
display value
empty
overflow protection