After mounting, wiring and setting check whether the unit operates
correctly.
At every power on the sensor initialises again. During this phase
ensure that the vessel is not completely filled.
If a mounting element (flange, etc.) is in the active zone, the level must
have a minimum distance to the lower edge of the mounting element
at power on:
The values are maintained if you follow the mounting recommenda-
tion
→
page 24).
Always carry out a reset in the following cases (disconnect the sensor
briefly and then connect it again) so that the sensor initialises again.
Observe the indications in the two tables above.
• If the sensor has been removed from the vessel and then inserted
again during operation.
• If the active zone of the sensor has been touched with the hand or
grounded objects (e.g. a screwdriver).
• After a change of media if the dielectric constants differ much (e.g.
oil/water).
Display during
operation
Level at power on
Reset
Page 27
ENGLISH
Installation and set-up / operation
switch on, initialisation
flashing: level close to the maximum measured value
level below the active zone
flashing = short circuit in switching output 1, 2, 3 or 4
XXX / XX.X
...
LK8024
LK8023
LK8022
59.5
40.5
20
Max. level at power on
in cm from the lower edge of the sensor
LK8024
LK8023
LK8022
8
5
3
Minimum distance between the medium and
mounting element in the active zone [cm]