Bedienungsanleitung

Operating instructions

Notice utilisateurs

Elektronischer 

Füllstandssensor

Electronic level sensor 

Détecteur de niveau 

électronique

LK8

R

Sachnr

. 701615/05       09/03

DEUTSCH

ENGLISH

FRANÇAIS

Summary of Contents for Efector 160 LK8

Page 1: ...dienungsanleitung Operating instructions Notice utilisateurs Elektronischer F llstandssensor Electronic level sensor D tecteur de niveau lectronique LK8 R Sachnr 701615 05 09 03 DEUTSCH ENGLISH FRAN A...

Page 2: ...age 23 Installation page 24 Electrical connection page 25 Programming page 26 Installation and set up operation page 27 Technical information Functioning Parameters page 28 Table of binary values page...

Page 3: ...Structure du menu M S M M M RUN RUN M S M M S M M S M M S M M S M M S M M S M M S M S M M S M M S M M S M M S M M S M M S M M S M M S M S M M M RUN RUN M S M M M S M M S M M S M S M Mode Enter Set M S...

Page 4: ...nung auf andere Einheiten und erhalten exakt die gew nschten Werte Decrease the value Let the display of the parameter value move to the maximum setting value Then the cycle starts again at the minimu...

Page 5: ...en der Parameterwerte Einstelltaste Set Einstellen der Parameterwerte kontinuierlich durch Dauerdruck schrittweise durch Einzeldruck 1 2 3 4 30 5 64 M12 x1 I L 16 50 51 8 5 A 2 1 3 M LK8022 LK8023 LK8...

Page 6: ...g Mode 16 stufige Analogauswertung mit einer Aufl sung von 6 25 des Me bereichs Bin rmodus Binary Mode Die Ausg nge OUT1 OUT 4 geben f r jede Stufe einen 4 stelligen Wert im 8 4 2 1 Bin rcode aus Wert...

Page 7: ...rke lschicht auf Wasser oder ein Wassersumpf am Grunde eines mit l gef llten Beh lters Hinweis Ein d nner lfilm einige mm auf Wasser oder wasser basierte Medien beeintr chtigt die Funktion des Sensors...

Page 8: ...bt es im Arbeitsbetrieb Unabh ngig davon k nnen die eingestellten Parameterwerte abgelesen werden Kurzer Druck auf die Taste Mode Enter bl ttert durch die Para meter Kurzer Druck auf die Taste Set zei...

Page 9: ...itte des Beh lters Bei verschmutzten Medien wird empfohlen Befestigen Sie das Ger t in einer Zone in der das Medium stark in Bewegung ist z B am Zulauf Bei Einbau in metallische Steigrohre Bypass mu d...

Page 10: ...ien z B le und zur Erf llung der CE Richtlinien nach dem EMV Gesetz mu das Sensor geh use elektrisch mit Erde verbunden werden Dies geschieht dadurch da der aufmontierte Erdungsring oder eine entsprec...

Page 11: ...ode Enter Set Mode Enter Set Dr cken Sie die Taste Mode Enter bis der gew nschte Parameter im Display erscheint Dr cken Sie die Taste Set und halten Sie sie gedr ckt Der aktuelle Parameterwert wird 5s...

Page 12: ...nitialisiert Beachten Sie dabei die Angaben in den beiden Tabellen oben Wenn der Sensor w hrend des Betriebs aus dem Beh lter gezogen und wieder eingeschoben wurde Wenn der aktive Bereich des Sensors...

Page 13: ...2 47 9 17 4 18 9 1 1 0 1 13 7 14 9 5 4 5 9 27 4 29 8 10 8 11 7 40 6 44 2 16 0 17 4 0 1 0 1 12 5 13 7 5 0 5 4 24 9 27 4 9 8 10 8 36 9 40 6 14 5 16 0 1 0 0 1 11 3 12 5 4 4 5 0 22 5 24 9 8 9 9 8 33 3 36...

Page 14: ...LO erscheint Dr cken Sie die Set Taste und halten Sie sie fest bis die Anzeige erscheint Dr cken Sie dann kurz die Mode Enter Taste Unit Anzeigeeinheit Es sind 2 Einstellungen w hlbar EU Anzeige in cm...

Page 15: ...Gutbereich Fnc Hysteresefunktion Fensterfunktion Seite 15 DEUTSCH R ckschaltpunkt Unterer Grenzwert bei dem der Ausgang seinen Schaltzustand ndert rP1 rP4 sind nur aktiv wenn der Bin rmodus ausgescha...

Page 16: ...Santoprene FPM Viton Messing optalloybeschichtet NBR Buna N PA PBTP Pocan PC Macrolon PP Polypropylen Werkstoffe in Kontakt mit dem Medium PP Polypropylen Schutzart Schutzklasse IP 67 III Umgebungste...

Page 17: ...vor 8 4 2 1 Bin rcode Wertetabelle Seite 13 Vorratsbeh lter F llstands berwachung Seite 17 DEUTSCH Applikationen Men Einstellung bin on Die Einstellungen f r SPx rPx und OUx sind nicht wirksam OFS Bin...

Page 18: ...US gesetzt Alarmmeldung Min Wert unterschritten Drahtbruch Vorlage bzw Druckerh hungs beh lter F llstandsregelung und Min Max ber wachung mit 4 Schaltausg ngen bin OFF Ersetzt 4 Schwimmerschalter Seit...

Page 19: ...beanlage Beh lter entleeren berf llsicherung realisiert mit 3 Schaltausg ngen bin OFF Ersetzt 3 Schwimmerschalter Seite 19 DEUTSCH Applikationen Konfiguration der Schaltausg nge 1 3 Maximalwert bersch...

Page 20: ...gement of the parameter values Set button setting of the parameter values scrolling by holding pressed incremental by pressing briefly 1 2 3 4 30 5 64 M12 x1 I L 16 50 51 8 5 A 2 1 3 M LK8022 LK8023 L...

Page 21: ...tion with a resolution of 6 25 of the measur ing range The outputs OUT1 OUT4 provide a 4 digit value in the 8 4 2 1 bina ry code for each step table of values page 28 Switching mode Binary mode Page 2...

Page 22: ...al cm thick or a water layer at the bottom of a vessel filled with oil Note A thin oil film a few mm on water or water based media does not affect the function of the sensor Applications Measuring ran...

Page 23: ...sensing processing and output functions of the unit continue as if in Run mode The parameter names are scrolled with each pressing of the Mode Enter button When the Set button is pressed briefly the c...

Page 24: ...it is installed in small plastic vessels For dirty media we recommend Fasten the unit in a zone where there is much movement of the medium e g at the supply inlet When installed in metal rising pipes...

Page 25: ...lectri cally connecting the pre mounted earthing ring or a corresponding fix ture to ground e g the vessel wall The sensor uses the ground or the vessel potential as a reference This means that a meas...

Page 26: ...rogramming 1 Mode Enter Set Mode Enter Set Mode Enter Set Press the Mode Enter button several times until the respective parameter is displayed Press the Set button and keep it pressed The current par...

Page 27: ...dications in the two tables above If the sensor has been removed from the vessel and then inserted again during operation If the active zone of the sensor has been touched with the hand or grounded ob...

Page 28: ...47 9 17 4 18 9 1 1 0 1 13 7 14 9 5 4 5 9 27 4 29 8 10 8 11 7 40 6 44 2 16 0 17 4 0 1 0 1 12 5 13 7 5 0 5 4 24 9 27 4 9 8 10 8 36 9 40 6 14 5 16 0 1 0 0 1 11 3 12 5 4 4 5 0 22 5 24 9 8 9 9 8 33 3 36 9...

Page 29: ...r LO is displayed Press the Set button and keep it pressed until is displayed Then press the Mode Enter button briefly Display unit 2 settings can be selected EU display in cm Europe inc display in in...

Page 30: ...0 Technical information Functioning Parameters Switch off point Lower limit value at which the output changes its switching status rP1 rP4 are active only if binary mode is not active bin OFF Dependen...

Page 31: ...using material EPDM X Santoprene FPM Viton Optalloy plated brass NBR Buna N PA Pocan PC Macrolon PP polypropylene Materials wetted parts PP polypropylene Protection IP 67 III Operating temperature C 0...

Page 32: ...tal form 8 4 2 1 binary code table of values page 28 Storage vessels Level monitoring Page 32 Applications Menu setting bin on The settings for SPx rPx and Oux are not effective OFS Binary value OUT1...

Page 33: ...value wire break Storage vessel Monitoring of the acceptable range alarm and level control with 4 switching outputs bin OFF Replaces 4 float switches Page 33 ENGLISH t L SP1 SP2 1 0 OFS OUT1 Hnc 1 0...

Page 34: ...e vessel overflow protection with 3 switching out puts bin OFF Replaces 3 float switches Page 34 Applications Configuration of the switching outputs 1 3 maximum value exceeded alarm hysteresis functio...

Page 35: ...lage des valeurs de param tre en appuyant sur le bouton poussoir et le maintenant appuy pas pas en appuyant sur le bouton poussoir plusieurs fois 1 2 3 4 30 5 64 M12 x1 I L 16 50 51 8 5 A 2 1 3 M LK80...

Page 36: ...apes code binaire avec une r solution de 6 25 de l tendue de mesure mode binaire Binary Mode Les sorties OUT1 OUT4 fournissent une valeur de 4 chiffres en code binaire 8 4 2 1 pour chaque tape tableau...

Page 37: ...e l eau ou une cou che d eau au fond d une cuve remplie d huile Remarque Une mince couche d huile quelques mm sur de l eau ou des fluides base d eau n affecte pas la fonction du d tecteur Applications...

Page 38: ...am tre r gl es peuvent tre lues Si le bouton poussoir Mode Enter est appuy bri vement les param tres sont parcourus Si le bouton poussoir Set est appuy bri vement la valeur du param tre correspondante...

Page 39: ...nter l ap pareil au milieu de la cuve si possible En cas de fluides souill s Fixer l appareil dans une zone o le fluide bouge fortement par ex sur l alimentation En cas de montage dans des tuyaux vert...

Page 40: ...nt l anneau de masse pr mont ou en utilisant une fixation correspon dante raccord e lectriquement la terre par ex paroi de la cuve Le d tecteur utilise la terre le potentiel de la cuve comme r f rence...

Page 41: ...ton Mode Enter plusieurs fois jusqu ce que le param tre d sir soit affich Appuyer sur le bouton Set et le maintenir appuy La valeur de param tre actuelle clignote pendant 5s apr s la valeur est incr m...

Page 42: ...cations dans les deux tables ci dessus Lorsque le d tecteur a t enlev de la cuve et ins r de nouveau durant le fonctionnement Lorsque la zone active du d tecteur a t touch e par la main ou des objets...

Page 43: ...8 10 8 11 7 40 6 44 2 16 0 17 4 0 1 0 1 12 5 13 7 5 0 5 4 24 9 27 4 9 8 10 8 36 9 40 6 14 5 16 0 1 0 0 1 11 3 12 5 4 4 5 0 22 5 24 9 8 9 9 8 33 3 36 9 13 1 14 5 0 0 0 1 10 0 11 3 3 9 4 4 20 1 22 5 8...

Page 44: ...soit affich Appuyer sur le bouton Set et le maintenir appuy jusqu ce que soit affich Appuyer bri vement sur le bouton Mode Enter Unit affich e 2 r glages peuvent tre s lectionn s EU affichage en cm E...

Page 45: ...nformations techniques Fonctions Param tres Point de consigne bas Seuil auquel la sortie change son tat de commutation rP1 rP4 ne sont actifs que si le mode binaire n est pas activ bin OFF D pendence...

Page 46: ...PBTP Pocan PA PC Macrolon PP polypropyl ne Mati res en contact avec le fluide PP polypropyl ne Protection IP 67 III Temp rature ambiante C 0 60 Temp rature du fluide C Huile 0 65 Liquides d arrosage...

Page 47: ...leau de valeur page 44 Cuve de stockage Surveillance de niveaux Page 48 Applications R glage du menu bin on Les r glages pour SPx rPx et OUx ne sont plus effectifs OFS Bin rwert OUT1 OUT2 OUT3 OUT4 1...

Page 48: ...ptu re d un fil Cuve de stockage Surveillance de la plage acceptable alarme et r gulation du niveau avec 4 sorties de commua tion bin OFF Remplace 4 interrupteurs flotteur Page 49 FRAN AIS t L SP1 SP2...

Page 49: ...en berf llsicherung realisiert avec 3 sorties de commua tion bin OFF Remplace 3 interrupteurs flotteur Applications configuration des sorties de commutation 1 3 au dessus de la valeur max alarme fonct...