background image

CR0708 CR0709

3

1 Preliminary note

You will find instructions, technical data, approvals, accessories and further information using the QR
code on the unit / packaging or at www.ifm.com.

1.1 Symbols used

Requirement

Instructions

Reaction, result

[...]

Designation of keys, buttons or indications

Cross-reference

Important note

Non-compliance may result in malfunction or interference.

Information

Supplementary note

1.2 Warnings used

ATTENTION

Warning of damage to property

CAUTION

Warning of personal injury

w

Slight reversible injuries may result.

WARNING

Warning of serious personal injury

w

Death or serious irreversible injuries may result.

Summary of Contents for ecomatController CR0708

Page 1: ...Operating instructions ecomatController CR0708 CR0709 HW version V3 0 0 x 11494095 00 12 2022 GB...

Page 2: ...5 5 Fastening 8 6 Electrical connection 10 6 1 Wiring 10 6 2 Connection technology 10 6 3 Shield connection 11 6 4 Fuses 11 6 5 Laying of the supply and signal cables 12 6 5 1 GND connections 13 6 6...

Page 3: ...ructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result in malfunction or interference Information Supplementary note 1 2 Warnings...

Page 4: ...ent before setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental conditions without any restrictions Only...

Page 5: ...connected and used depending on the required input and or output type Connection of sensors or actuators via CAN interfaces Connection to other controllers via CAN Only use the device within the limit...

Page 6: ...shield connection 4 protective covers 1 operating instructions CE Declaration of Conformity u In the event of incomplete or damaged items supplied please contact ifm Programming manual and software fi...

Page 7: ...rried out by qualified personnel u Remove and cover the plus and minus terminals of the batteries u Disconnect all contacts of the device from the on board system prior to welding on the vehicle or ma...

Page 8: ...ceeded w If housing temperatures presenting a danger to people are reached u Cover housing to prevent unintentional contact u Apply warning for hot surfaces visibly on the device 5 4 Installation posi...

Page 9: ...he housing w Damage to the device u Do not use stainless steel screws or nickel plated screws u Use zinc plated screws u In very corrosive environments such as extremely salty air use screws with surf...

Page 10: ...n w Reverse polarity protection is only ensured in case of supply via the on board system via a battery if the polarity of the supply is reversed as a whole battery connected incorrectly The basic pri...

Page 11: ...se a minimum category 5 Cat 5 cable The RS 232 interface serves only as a service interface e g for firmware updates 6 3 Shield connection 1 1 Holes for shield connection To ensure the protection of t...

Page 12: ...ed example CR0709 1 GND star point Bridging of connections in the connectors is not permitted RESET COM is a service input see programming manual u For the operation of the controller connect RESET CO...

Page 13: ...D star point WARNING Wrong connection of the GND connections w Loss of the correct function the measurement accuracy and EMC possible u Do not connect the GNDANA GNDRES and GNDOVA connections to the c...

Page 14: ...the analogue inputs A example CR0709 u Connect GNDANA to GND of the signal source Do not connect GNDANA to other GND connections or the common GND star point 6 7 Resistor inputs controller VBB 30 nn...

Page 15: ...e digital inputs CSO controller VBB 30 nn VBB 15 nn VBB 0 nn VBB 1 nn VBB 2 nn GND SYS nn GND 1 2 nn input BH FRQH nn input BH FRQH nn GNDANA nn nn GNDRES Shield supply 1 Fig 7 Connection of the high...

Page 16: ...on of the analogue outputs A example CR0709 The controller can be connected to the following loads resistive loads The connected load must not exceed the maximum permissible values of the respective o...

Page 17: ...ult currents to flow through the controller and load which lead to an undefined state of the controller and the system w Loss of correct function u Always connect the ground lead of the controller and...

Page 18: ...roller can be connected to the following loads resistive loads capacitive loads adapt diagnostic settings to the load see programming manual inductive loads The connected load must not exceed the maxi...

Page 19: ...input 24 V 12V nn input nn GNDANA nn nn input nn sensor sensor sensor load load load GNDOVA Shield nn GNDRES Fig 11 Example connection to 24 V and 12 V power supply combined example CR0709 The operat...

Page 20: ...formation about installation and set up see the programming manual Required components Suitable CODESYS version CODESYS plug ins CODESYS package for the controller Firmware note check firmware version...

Page 21: ...n case of malfunction u Do not open the housing as the unit does not contain any components which can be maintained by the user The unit must only be repaired by the manufacturer u Clean the device us...

Reviews: