PROCESS AND DIALOGUE MODULE
PDM 360
COMPACT
PAGE
32
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen
28.01.2015
We reserve the right to make technical alterations without prior notice.
CR1056 / page 3
CR1056
Characteristics of the inputs / outputs
Inputs
%IX0.00...01 (B
L
)
■
Digital inputs for positive sensor signals
can be configured as ...
switch-on level
0.7 U
B
switch-off level
0.4 U
B
input resistance
3.2 k
Ω
input frequency
max. 50 Hz
Outputs
%QX0.00...01 (B
H
)
■
Semiconductor outputs
can be configured as ...
positive switching (high side), short-circuit and overload protected
switching voltage
10...32 V DC
switching current
max. 0.5 A (per output)
output frequency
max. 100 Hz (depending on the load)