DP2200
Analogue threshold display
18
[mA]
4
20
100.0
10
0.0
Fig. 9: Example with scaled display value
Menu setting example
ScAL
ccc.c
C.ASP
0.0
C.AEP
100.0
Input
10 mA
Display
37.5
8.4.7 coLr ─ display colours and colour changes
Assignment of the display colours "red" and "green" within the measuring range.
•
[rEd] = continuously red (independent of the measured value).
•
[GrEn] = continuously green (independent of the measured value).
•
[r1ou] = red when OUT1 switches.
•
[G1ou] = green when OUT1 switches.
OUT1
gn
rd
4 mA
20 mA
Fig. 10: Hysteresis function with [r1ou]
OUT1
rd
gn
4 mA
20 mA
Fig. 11: Hysteresis function with [G1ou]
FL1
FH1
gn
gn
rd
4 mA
20 mA
Fig. 12: Window function with [r1ou]
FL1
FH1
rd
rd
gn
4 mA
20 mA
Fig. 13: Window function with [G1ou]
[r-cF] = red when the measured value is between the values [cFL] and [cFH].
[G-cF] = green when the measured value is between the values [cFL] and [cFH].
8.4.8 cFH/cFL ─ upper/lower value for colour change
When setting [coLr] to [r-cF] or [G-cF]:
u
Select [cFH] and set the upper limit.
Setting range corresponds to the measured values. The lowest setting value is [cFL].
Select [cFL] and set the lower limit value.
Setting range corresponds to the measured values. The highest setting value is [cFH].