Installation instructions

Compact speed monitor M18 

DC design, IO-Link, with connector

 DI5029 

 DI5030

706454 / 00

 

10 / 2017

UK

Summary of Contents for DI5029

Page 1: ...Installation instructions Compact speed monitor M18 DC design IO Link with connector DI5029 DI5030 706454 00 10 2017 UK ...

Page 2: ...tching function normally closed 7 6 IO Link mode 7 6 1 LED display 8 6 2 Setting parameters via IO Link 8 6 2 1 Setting range and conditions for parameter setting 10 6 2 2 Start up delay 11 6 2 3 Background compensation 11 6 2 4 Teach offset 11 6 2 5 Prescaler 11 6 3 Diagnostics and events 12 7 Installation 13 7 1 Tips on flush and non flush mounting in metal 13 8 Electrical connection 14 8 1 Wiri...

Page 3: ...r maintenance of the device Read this document before use to familiarise yourself with operating conditions installation and operation Keep this document during the entire duration of use of the device WARNING Adhere to the warning notes and safety instructions 2 Safety instructions 1 1 Symbols and warnings used Instructions Cross reference Information Supplementary note Important note Non complia...

Page 4: ...sured value with the switching thresholds and switches the outputs according to the configuration The device can be operated in the IO Link mode or in the SIO mode switching output 4 Function diagrams 4 1 Single point mode Normally open switch point logic 1 SP1 switch off point SP1 hyst switch on point The open output status indicates that a set rotational speed has not been reached Normally close...

Page 5: ...ndow mode Normally open switch point logic 1 SP1 switch on point window SP1 hyst switch off point SP2 switch on point window SP2 hyst switch off point Normally closed switch point logic 0 SP1 switch off point window SP1 hyst switch on point SP2 switch off point window SP2 hyst switch on point ...

Page 6: ...6 2 3 4 1 1 Power on delay time 2 Start up delay 3 NO 4 NC ...

Page 7: ...g the start up delay Switched conducting On Rotational speed SP SP switch point Hy hysteresis 6 IO Link mode IO Link allows the configuration of internal parameters such as start up delay and switching behaviour normally closed normally open as well as reading the current measured values Furthermore IO Link protects against signal faults and measured value losses as well as tampering with the devi...

Page 8: ...pecific Tag Application Specific Tag max 32 bytes default P n Output polarity for the switching outputs PNP NPN default PNP SSC1 Param SP1 Setpoint 1 5 24000 pulses min default 5 pulses min SSC1 Param SP2 Setpoint 2 3 21600 pulses min default 3 pulses min SSC1 Config Logic Setpoint logic State for target detected NO NC default NO SSC1 Config Mode Setpoint mode single point window two point mode de...

Page 9: ...00 ms steps default 0 ms SSC2 Switch Off delay Switching signal channel 2 Switch Off delay 0 60000 ms 100 ms steps default 0 ms PrSC Prescaler indicates the number of targets to calculate current revolution 1 99 default 1 TI Select Teach selection SSC1 SSC2 default SSC1 Teach SP1 Teach switch point 1 Teach SP2 Teach switch point 2 Teach offset Sets an offset between setpoint and current process da...

Page 10: ... setting To properly set the device parameters the value line below has to be observed It gives important information about the setting range and the resulting conditions Conditions 5 SP1 24000 3 SP2 21600 Hy 10 2 Hy abs SP2 SP1 10 with SP1 SP2 2 1 min ...

Page 11: ...e for example Background compensation of the device adjusts the sensing range so that the sensor goes into an undamped state and it can detect the object again During background compensation there must not be any object in the desired detection range 6 2 4 Teach offset This parameter allows setting of an offset between the taught process value and the resulting switching value Example Teach offset...

Page 12: ... 545 BitCoded_ActiveEvents 35888 d 8C 30 h Process variable range under run Warning Process data uncertain Note This event will not be transmitted via IO Link Event mechanism it is only available by reading index 37 DetailedDeviceStatus or 545 BitCoded_ActiveEvents 36350 d 8D FE h Test Event 1 Warning Event appears by setting index 2 to value 240 Event disappears by setting index 2 to value 241 36...

Page 13: ...e using a bracket and secure it by means of the nuts provided so that it cannot work loose Adhere to the above mounting specifications to ensure a correct function 7 1 Tips on flush and non flush mounting in metal Installation instructions cylindrical design 2xSn flush non flush ...

Page 14: ...h non flush Side by side installation only possible with different oscillator frequencies 8 Electrical connection Disconnect power Connect the device according to the wiring diagram 8 1 Wiring L L 1 4 3 L L 1 4 3 DI5029 DI5030 SIO 4 Switching output PNP NPN programmable via IO Link IO Link 4 IO Link communication Factory setting PNP normally open ...

Page 15: ...monitor 10 Scale drawing EPS Source Product Scale Drawing Frame Size 80 mm x 22 5 mm Original Scale Drawing MTD MZ_100_0701 M18 x1 M12 x1 45 49 60 LED 4 x 90 24 4 M18 x1 M12 x1 45 49 60 LED 4 x 90 24 4 EPS Source Product Scale Drawin Frame Size 80 mm x Original Scale Drawing P_MZ_100_0702 M18 x1 35 10 M12 x1 60 LED 4 x 90 49 24 4 M18 x1 35 10 M12 x1 60 LED 4 x 90 49 24 4 DI5029 DI5030 Dimensions m...

Page 16: ...16 ...