background image

Electronic circuit breakers, standard

DF11xx DF12xx DF25xx

9

7 Operating and display elements

2

3

4

1

Fig. 2: Example DF11xx supply module

2

3

4

1

Fig. 3: Example DFx2xx circuit protection module

7.1 DF12xx circuit protection modules

The different operating states of the circuit protection modules are indicated by the status LED.

Status LED

Operating status

Status of load output

off

Missing operating voltage, error in initialisation or chan-
nel switched off via button

off

green

on

Channel switched on, no fault

on

green/orange

flashing

Load current limit reached

on

orange

on

Overload or short circuit until disconnection

on

Channel switched off

off

red

on

Triggering via short circuit or overload

off

Undervoltage in ON status with automatic switching on
again

Tab. 1: Status LED DF12xx circuit protection modules

7.2 Interrogation of module to confirm the set nominal current

Only for circuit protection modules with adjustable nominal current.

u

Press the ON/OFF/reset button of the requested channel between 2 and 5 seconds.

w

The status LED of the selected channel flashes red once.

w

The status LED flashes orange to display the set nominal current. The LED flashes red once to
confirm completion of the cycle. The LED flashes orange, once or multiple times, in accordance
with nominal current setting in amperes (orange flashing once = 1 A; orange flashing twice = 2 A;
etc.).

w

The set nominal current is displayed five times. After 5 cycles the display changes to the current
operating status.

u

To interrupt/stop the interrogation cycle, and return to normal status indication mode, press the ON/
OFF/reset button of the requested channel at any time.

Summary of Contents for DF11 Series

Page 1: ...Operating instructions Electronic circuit breakers standard for the 24 V DC secondary circuit DF11xx DF12xx DF25xx 11367179 00 09 2022 GB...

Page 2: ...perature factor continuous current rating 6 4 2 Fail safe element 6 5 Installation 7 6 Electrical connection 8 6 1 Supply feedback and potential modules 8 7 Operating and display elements 9 7 1 DF12xx...

Page 3: ...data approvals and further information using the QR code on the unit packaging or at www ifm com 1 1 Symbols used Requirement Instructions Reaction result Designation of keys buttons or indications Cr...

Page 4: ...ot adhered to personal injury and or damage to property may occur The manufacturer assumes no liability or warranty for any consequences caused by tampering with the product or incorrect use by the op...

Page 5: ...x DF25xx 5 3 Intended use Electronic overcurrent protection for primary switched mode 24V DC power supplies A supply module must be combined with at least one circuit protection module and optionally...

Page 6: ...tallation area IP 20 operating area Electrical connection Type push in terminals contact lever strip applicable 4 1 Temperature factor continuous current rating The time current characteristic curve d...

Page 7: ...rcuit breakers standard DF11xx DF12xx DF25xx 7 5 Installation u Mount the devices on a 35 mm rail 2 3 4 1 Fig 1 Example circuit protection module DF12xx 1 Rail 2 Contact lever 3 Installation area 4 Op...

Page 8: ...2 mm wide micro screwdriver As soon as the supply module is supplied with voltage the device closes the contacts connected to terminals 13 and 14 If a fault occurs at one or several of the connected...

Page 9: ...status with automatic switching on again Tab 1 Status LED DF12xx circuit protection modules 7 2 Interrogation of module to confirm the set nominal current Only for circuit protection modules with adj...

Page 10: ...seconds w The status LED of the selected channel flashes red once w The status LED slowly flashes green max 10 times then red once u Press the ON OFF reset button of this channel when the LED signals...

Page 11: ...e free Only the manufacturer is allowed to repair the unit u After use dispose of the device in an environmentally friendly way in accordance with the applicable national regulations Cleaning the unit...

Reviews: