IO-Link master with EtherCAT interface DataLine 4 ports IP 65 / IP 66 / IP 67
80
•
Acknowledge Mode: Events will only be overwritten, when they are read and acknowledged.
The configuration is done via sub-index 0x05. The eventsare stored in sub-indexes 0x06...0x26.
>
9.3.9
Configure IO-Link devices
33881
The IO-Link master supports the configuration of the connected IO-Link devices from the EtherCAT
projection software. The parameters of an IO-Link device are set via IO-Link index and subindex. The
number of the configurable parameters depends on the connected IO-Link device.
Available parameters of the IO-Link devices:
→ IO Device Description (IODD) of the IO-Link
device
The user can read and write IO-Link index and subindex using the following methods:
•
Acyclic communication:
→
Use acyclic services
(