30
ifm
Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 69K (AL1101)
2017-05-31
Configuration
>
8.1.3
Offline parameter setting
SYS_OBJECTID>
The AL1101 supports the offline parameter setting. In this context, the user creates and stores a
configuration for the unit and the connected IO-Link devices without being connected to the AL1101.
The configuration created in this way can be stored as a file (*.lrp) and loaded to the device and
activated at a later date.
Further information about offline parameter setting:
→ Operating instructions of the parameter
setting software LR DEVICE
>
8.1.4
VPN connection
22762
An active VPN connection blocks the access of the parameter setting software LR DEVICE to
the Profinet interface of the AL1101.
► Deactivate the VPN connection in order to be able to access the AL1101 with the LR
DEVICE.
Summary of Contents for AL1101
Page 76: ......