![background image](http://html1.mh-extra.com/html/ifm/ac6002/ac6002_operating-instructions-manual_620627083.webp)
IO-Link Master with AS-Interface Interface StandardLine 2 Ports IP 65 / IP 66 / IP 67
83
>
Command request
59360
Byte
Bit
7
6
5
4
3
2
1
0
0
Block ID
1
0x0A
2
Target ID
3
Data Length
4
Index (LSB)
5
Index (MSB)
6
Sub-index
7
Parameter Data Length (n Bytes)
8
Parameter Data (Byte 1)
...
...
8+(n-1)
Parameter Data (Byte n)
(8+n)...160
ignored
Legend:
[Target ID]
Target of the required operation
8 bits
0x01
IO-Link Port 1
0x02
IO-Link Port 2
[Data Length]
Length of the request data in this segment (number of bytes)
8 bits
0x00
...
0
0x9C
156
[Index]
Index of the IO-Link object
Index = 0x1234
Index (MSB) = 0x12
Index (LSB) = 0x34
16 bits
per byte: 0x00...0xFF
[Subindex]
Subindex of the IO-Link object
8 bits
0x00...0xFF
[Parameter Data
Length]
Length of the parameter data (number of bytes n)
8 bits
0x00
0 byte
...
...
0xE8
232 bytes
[Parameter Data
(Byte m)]
Parameter data (m = 1...n)
m*8 bits per byte:: 0x00...0xFF