IO-Link Master with AS-Interface Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
75
>
13.3.7 0x05: Read Output Process Data
52136
The command reads the process data of the outputs of an IO-Link port of the IO-Link master.
>
Command request
52137
Byte
Bit
7
6
5
4
3
2
1
0
0
0x00
1
0x05
2
Target ID
3
0x00
4...160
ignored
Legend:
[Target ID]
Target of the required operation
8 bits
0x01
IO-Link port 1
0x02
IO-Link port 2
0x03
IO-Link port 3
0x04
IO-Link port 4