AC1253 Installation Manual 

 

 

 

 

Product Description 

The AC1253 is a DIN-rail mountable power supply for three-phase mains systems, which provides 
network power for the AS-Interface

®

 system. The AS-Interface

®

 system is a field bus technology, 

where power and data are provided by the same single two-conductor wire. Therefore, special power 
supplies with an integrated data-decoupling circuit are required to prevent the modulated signal 
voltage on the AS-Interface

®

 bus from being corrupted. 

 

Intended Use

 

This device is designed for installation in an enclosure and is intended for commercial use to supply 
power to AS-Interface

®

 network systems. 

Do not use this device in equipment, where malfunctioning may cause severe personal injury or 
threaten human life without additional appropriate safety devices, that are suited for the end-
application. 
If this device is used in a manner outside of its specification, the protection provided by the device may 
be impaired. 
When operating without AS-Interface structure (e.g. in a laboratory test), connect a 470μF/35V 
capacitor between AS-Int and AS-Interface – terminals to avoid output voltage oscillations. 
 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. Use ferrules for wires on the 
input terminals. Unused screw terminals should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20.

 

The housing does not provide 

protection against spilled liquids. 
The device is designed for overvoltage category II zones. Below 2000m altitude the device is tested 
for impulse withstand voltages up to 4kV, which corresponds to OVC III according to IEC 60664-1. 
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use 
without a proper PE (Protective Earth) connection. 
The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage 
between the input terminal and the PE potential must not exceed 400Vac. The device is not designed 
to be used on corner grounded delta systems. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in 
output current is required. 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL) without 
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A 
B- or 3A C-Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit. 
The green AS-i-OK LED reports a nominal output voltage of a running device. The LED is off as soon 
as the unit is in overload mode. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output 
shuts down and starts automatically again after cooling off. 
Do not parallel devices for higher output currents. 
Do not connect outputs of devices in a series connection for higher output voltages. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 36V. The output 
shuts down and automatically attempts to restart. 

 

Technical Data

 

All values are typical figures specified at 3x 400Vac 50Hz input voltage, 
symmetrical phase voltages, 30.6V 8A output load, 25°C ambient 
temperature and after a 5 minutes run-in time unless otherwise noted. 

Output voltage 

DC 30.6V 

Nominal 

Adjustment range 

Not adjustable 

Factory setting 30.6V 

Output current 

8A 

Below +60°C ambient  

 

6A 

At +70°C ambient 

 

Derate linearly b60°C and +70°C 

 

For use on AS-Interface

®

 networks only 

Current limitation 

>8.4A 

 

Input voltage AC 

3AC 380-480V 

-15% / +20% 

Mains frequency 

50 – 60Hz 

±6% 

Input current AC 

0.7 / 0.6A 

At 3x400 / 3x480Vac 

Power factor 

0.53 / 0.52 

At 3x400 / 3x480Va 

Input inrush current 

4 / 4A pk 

At 400 / 480Vac, temp. 
independent 

Efficiency 

92.0 / 92.1% 

At 3x400 / 3x480Va 

Power losses 

21.2 / 20.9W 

At 3x400 / 3x480Va 

Hold-up time 

34 / 53ms 

At 3x400 / 3x480Va 

Temperature range 

-25 to +70°C 

 

Max. wire size (litz wire) 

4mm² 

 

Wire size AWG 

AWG 20-10 

 

Max. wire diameter 

2.8mm 

 

Wire stripping length 

7mm / 0.28inch 

 

Tightening torque 

1Nm / 9lb.inch 

 

Size 

(wxhxd)

 

62x124x120mm 

Without DIN-rail 

Weight 

850g / 1.87lb 

 

 
 

Functional Diagram 

Input

Fuse

Input

Filter

Input

Rectifier

L1

Output

Overvoltage

Protection

PFC

Inductor

&

Inrush

Limiter

AS-i +

Output

Filter

AS-i-ok

(green)

Power

Converter

Shield

AS-i

Decoupling

Unit

AS-i +

AS-i -

AS-i -

Temperature

Shut-down

L2
L3

 

 
 

Output Characteristic 

Output voltage

12A

Output current

15V

0V

2A

4A

6A

0A

30.6V

8A

10A

 

 
 

Temperature Range 

Allowed output current

Ambient temperature

0A

-25

8A

+60

+70°C

6A

A: continuous

B: short term (max. 60s)

A

B

0

 

 