7
UK
Voltage output 0 ... 10 V
Factory setting
Measuring range scaled
P = system pressure, MEW = final value of the measuring range
In the set measuring range the output signal is between 0 and 10 V�
It is also indicated:
System pressure above the measuring range: output signal > 10 V�
Current output 4 ... 20 mA
Factory setting
Measuring range scaled
P = system pressure, MEW = final value of the measuring range
In the set measuring range the output signal is between 4 and 20 mA�
Also signalled:
• System pressure above the measuring range: output signal > 20 mA�
• System pressure below the measuring range: output signal 4���3�8 mA�