9.3 User settings (optional)
9.3.1 Setting the unit of measurement for the system pressure
► Select [Uni] and set the unit of measurement:
[bAr], [mbAr]
[MPA], [kPA]
[PSI]
[IH2O] (only PN2009, PN2027, PN2028, PN2069)
[inHG] (only PN2009)
[mmWS] (only PN2028)
9.3.2 Configuring the display
► Select [diS] and set update rate and orientation of the display:
[d1]: Update of the measured value every 50 ms�
[d2]: Update of the measured value every 200 ms�
[d3]: Update of the measured value every 600 ms�
[Ph]: Display of the measured peak value remains for a short time (peak
hold)�
[rd1], [rd2], [rd3], [rPh]: Display like d1, d2, d3, Ph; rotated by 180°�
[OFF]: The display is deactivated in the operating mode�
9.3.3 Zero-point calibration
► Select [COF] and set a value between -5 % and 5 % of the final value of
the measuring range (for PN2009 and PN2069 ± 5 % of the span)� The
internal measured value “0” is shifted by this amount�
Resets the calibration set by COF to the value set at the factory�
► Press [Mode/Enter] until [CAr] is displayed�
► Press [Set] and keep it pressed until [----] is displayed�
► Press [Mode/Enter] briefly�
9.3.4 Setting the delay time for the switching outputs
[dS1] / [dS2] = switch-on delay for OUT1 / OUT2�
[dr1] / [dr2] = switch-off delay for OUT1 / OUT2�
► Select [dS1], [dS2], [dr1] or [dr2], set value between 0�1 und 50 s (at 0�0
the delay time is not active)�