Read the product description before installing the unit. Ensure that the product
•
is suitable for your application without any restrictions.
Non-adherence to the operating instructions or technical data can lead to
•
personal injury and/or damage to property.
In all applications check compliance of the product materials (→ 6 Technical
•
data) with the media to be measured.
For units with cULus approval and the scope of validity cULus:
The device shall be supplied from an isolating transformer having a secondary
Listed fuse rated either
a) max 5 amps for voltages 0~20 Vrms (0~28.3 Vp) or
b) 100/Vp for voltages of 20~30 Vrms (28.3~42.4 Vp).
2 Function and features
The pressure monitor detects the system pressure and generates 1 output signal.
In case of increasing pressure the output closes when the Set1 value is
•
reached.
In case of decreasing pressure the output opens when the value „Set1 minus
•
hysteresis“ is reached.
The hysteresis is fixed (2% of value of measuring range).
Applications
Type of pressure: relative pressure
Order no.
Measuring range
Permissible
overload pressure
Bursting
pressure
bar
PSI
bar
PSI
bar
PSI
PK5520
0...400
0...5 800
600
8 700
1 600
23 200
PK5521
0...250
0...3 625
400
5 800
1 000
14 500
PK5522
0...100
0...1 450
200
2 900
1 000
14 500
PK5523
0...25
0...363
60
870
500
7 253
PK5524
0...10
0...145
25
362
300
4 350
Avoid static and dynamic overpressure exceeding the given overload
pressure.
Even if the bursting pressure is exceeded only for a short time the unit can
be destroyed (danger of injuries)!
ARIES TECHNOLOGY s.r.l.