1 Safety instructions

Read the product description before installing the unit. Ensure that the product 

• 

is suitable for your application without any restrictions.

Non-adherence to the operating instructions or technical data can lead to 

• 

personal injury and/or damage to property.

In all applications check compliance of the product materials (→ 6 Technical 

• 

data) with the media to be measured.

For units with cULus approval and the scope of validity cULus: 

The device shall be supplied from an isolating transformer having a secondary 

Listed fuse rated either 

a) max 5 amps for voltages 0~20 Vrms (0~28.3 Vp) or 

b) 100/Vp for voltages of 20~30 Vrms (28.3~42.4 Vp).

2 Function and features

The pressure monitor detects the system pressure and generates 1 output signal. 

In case of increasing pressure the output closes when the Set1 value is 

• 

reached.

In case of decreasing pressure the output opens when the value „Set1 minus 

• 

hysteresis“ is reached.

The hysteresis is fixed (2% of value of measuring range).

Applications

Type of pressure: relative pressure

Order no.

Measuring range

Permissible 

overload pressure

Bursting

pressure

bar

PSI

bar

PSI

bar

PSI

PK5520

0...400

0...5 800

600

8 700

1 600

23 200

PK5521

0...250

0...3 625

400

5 800

1 000

14 500

PK5522

0...100

0...1 450

200

2 900

1 000

14 500

PK5523

0...25

0...363

60

870

500

7 253

PK5524

0...10

0...145

25

362

300

4 350

Avoid static and dynamic overpressure exceeding the given overload

pressure.

Even if the bursting pressure is exceeded only for a short time the unit can 

be destroyed (danger of injuries)!

ARIES TECHNOLOGY s.r.l.

Summary of Contents for PK5520

Page 1: ...Installation Instructions Electronic pressure monitor PK55xx 704522 00 07 2009 UK ARIES TECHNOLOGY s r l ...

Page 2: ...tures The pressure monitor detects the system pressure and generates 1 output signal In case of increasing pressure the output closes when the Set1 value is reached In case of decreasing pressure the output opens when the value Set1 minus hysteresis is reached The hysteresis is fixed 2 of value of measuring range Applications Type of pressure relative pressure Order no Measuring range Permissible ...

Page 3: ...t must be observed Voltage supply to EN50178 SELV PELV Disconnect power before connecting the unit 5 Setting Operation locking ring 1 setting ring manually adjustable after unlocking 2 green LED supply voltage O K 3 process connection G A tightening torque 25 Nm 4 setting marks 5 yellow LED Set1 value reached output ON 6 sealing FPM DIN 3869 14 7 internal thread M5 8 To obtain the setting accuracy...

Page 4: ...g range 10 K 0 5 in the temperature range C 0 80 Operating temperatur C 25 80 Medium temperature C 25 80 Protection IP 67 III Insulation resistance MΩ 100 500 V DC Shock resistance g 50 DIN IEC 68 2 27 11ms Vibration resistance g 20 DIN IEC 68 2 6 10 2000 Hz Housing material Pocan PC Macrolon FPM Viton stainless steel 316S12 Materials wetted parts stainless steel 316S12 seal FPM Viton EMC EN 61000...

Page 5: ...5 UK 7 Scale drawing Dimensions are in millimeters 25 4 mm 1 inch 1 tightening torque 25 Nm 2 sealing FPM DIN 3869 14 ARIES TECHNOLOGY s r l ...

Reviews: