25
UK
10.2 Entering the probe length (unit on delivery)
On delivery of the unit, you must first enter the probe length� The complete
parameter setting menu cannot be accessed before this�
Malfunctions may occur if the wrong probe length is set�
►
Apply operating voltage�
> The initial display
is shown�
►
Select [LEnG], press [Set] for 5 s�
> [nonE] is displayed�
►
Enter the probe length in inch� Remarks on the determination of the
probe length → 6.3.
►
Briefly press [Mode/Enter]�
Then the unit changes to the operating mode� For further parameter setting the
menu can be opened� The parameter [LEnG] can be accessed and modified just
like all other parameters�
10.3 Configuration of the display
►
Select [Uni] and set the unit of measurement: [cm], [inch]�
Factory setting: inch�
►
Select [SELd] and set type of indication:
-[L] = The level is indicated in cm or inch�
-[L%] = The level is indicated in percent of the final value of the
measuring range�
-[OFF ] = The display is switched off in the operating mode� When one
of the buttons is pressed, the current measured value is displayed for
15 s� The LEDs remain active even if the display is deactivated�
10.4 Offset setting
►
Select [OFS] and enter the distance between bottom of the tank and
lower edge of the probe�
Afterwards, display and switch points refer to the real level� Factory setting:
[OFS] = 0�
Note: Set [OFS] before setting the switching limits (SPx/FHx, rPx/FLx)�
Otherwise, the switching limits shift by the value of the set offset�