36
15 Applications
15.1 Storage tank
Level control and min / max monitoring with 4 switching outputs
Replaces 4 float switches
Configuration of the switching outputs 1...4
SP1
Maximum value exceeded
→ alarm.
ou1
Hysteresis function, normally closed (Hnc).
SP2
Upper preset value exceeded
→
finish refilling.
ou2
Hysteresis function, normally open (Hno).
SP3
Below lower preset value
→ start refilling.
ou3
Hysteresis function, normally closed (Hnc).
SP4
Below min. value
→ alarm.
ou4b
Hysteresis function, normally open (Hno).
rP1...4 Each slightly below SPx to suppress wave movements.
t
L
SP1
SP2
1
0
OUT1
Hnc
1
0
OUT2
Hno
SP3
SP4
1
0
OUT3
Hnc
1
0
OUT4
Hno
OFS