21
UK
9.6.2 Configuration of the standard display
► Select [SELd] and determine the standard measuring unit�
-[FLOW] = the current volumetric flow value in the standard unit of
measurement is displayed
-[TOTL] = the current meter reading in Nm
3
or 1000 Nm
3
is displayed�
-[TEMP] = the current medium temperature in °C is displayed
► Select [diS] and set the update rate and orientation of the display�
-[d1] = update of the measured values every 50 ms
-[d2] = update of the measured values every 200 ms
-[d3] = update of the measured values every 600 ms
-[rd1], [rd2], [rd3] = display as for d1, d2, d3; rotated by 180°
-[OFF] = the display is switched off in the operating mode; when press-
ing the button the process value is displayed for 15 s�
9.6.3 Setting of measured value damping
► Select [dAP] and set the damping constant in seconds (t value 63 %)�
9.6.4 Setting of the error behaviour of the outputs
► Select [FOU1] and set the value
-[On] = output 1 switches ON in case of a fault�
-[OFF] = output 1 switches OFF in case of a fault�
> For both values ([ON] and [OFF]) the counter stops counting in case of
a fault�
-[OU] = output 1 switches irrespective of the error as defined with the
parameters�
► Select [FOU2] and set the value
-[On] = output 2 switches ON in case of a fault, the analogue signal
goes to the upper end stop value (22 mA)�
-[OFF] = output 2 switches OFF in case of a fault, the analogue signal
goes to the lower end stop value (3�5 mA)�
-[OU] = output 2 switches irrespective of the error as defined with
the parameters� The curve of the analogue signal corresponds to
IEC60947-5-7 (→ diagram in 4.6).
9.6.5 Setting of the standard pressure to which the measured and display
values for volumetric flow refer
► Select [rEF�P] and set the requested standard pressure�
Setting range: 950���1050 hPa in steps of 1 hPa�