20
9.4.5 Counter reset using an external signal
► Select [OU2] and [InD]�
► Select [Din2] and set the reset signal�
-[HIGH] = reset for high signal
-[LOW] = reset for low signal
-[+EDG] = reset for rising edge
-[-EDG] = reset for falling edge
LED 7 (→ 7 Operating and display elements) indicates the input status
also with an active external reset�
9.5 Settings for temperature monitoring
9.5.1 Settings for limit value monitoring with OUT2
► Select [SEL2] and set [TEMP]�
► Select [OU2] and set the switching function�
-[Hno] = hysteresis function/NO
-[Hnc] = hysteresis function/NC
-[Fno] = window function/NO
-[Fnc] = window function/NC
► Select [SP2] and set the value at which the output switches�
► Select [rP2] and set the value at which the output switches back�
9.5.2 Setting the analogue value for temperature
► Select [SEL2] and set [TEMP]�
► Select [OU2] and set the function�
-[I] = temperature-proportional current signal (4…20 mA)
► Select [ASP] and set the value at which the minimum value is provided�
► Select [AEP] and set the value at which the maximum value is provided�
9.6 User settings (optional)
9.6.1 Setting of the standard unit of measurement for volumetric flow
► Select [Uni] and set the unit of measurement�
-[Lmin] = volumetric flow quantity in standard litres / minute
-[nm3h] = volumetric flow quantity in standard cubic metres / hour
-[nmS] = current flow velocity in standard metres / second
The setting only has an effect on the volumetric flow value�