12
4.3.2 Mount E3D304 for vertical operation of the device
Below you find a description how to mount the article E3D304 for vertical
operation of the device�
As the heat sinks and heat conductors are pre-mounted for horizontal operation of
the device, the heat sinks must be rotated by 90 degrees�
Follow the instructions:
1� Loosen countersunk head screws
④
�
2� Rotate both heat sinks
②
by 90 degrees�
> The cooling fins must be aligned vertically (see figure on the right)�
3� Place both heat sinks
②
on the bore holes of the heat conductors
①
�
4� Tighten countersunk head screws
④
with maximum 2,0 - 3,0 Nm�
5� Hold the heat conductors
①
on the device sides
⑧
�
> The hooks
③
of the heat conductors
get caught in the front of the device.
6� Insert nuts
⑦
in the heat conductor and tighten by hand with
cylinder head
bolts M5x75
⑤
�
7� Align the heat conductors
①
in a straight line to the device�
8� Tighten set screws
⑥
evenly�
> Tightening reduces the distance between the heat conductor and the device�
The heat conductor must lie flat on the device without air gap�
①
②
④
③