2

Remarks for safe use in hazardous areas

Functions and features

•  Use in hazardous areas according to the classification

II 3D

 (group II, category 3D, apparatus for dust atmosphere).

The requirements of the standards EN 60079-0 and EN 60079-31 are met. 

•  Marking (see unit or technical data sheet)

II 3D Ex tc IIIC T80°C Dc X IP67

•  Permissible operating temperature of the application (proper usage):

Ta: -20°C...+60°C

Installation / Set-up

The units must only be installed, connected and set up by qualified staff. The qualified staff 
must have knowledge of protection classes, regulations and provisions for apparatus in 
hazardous areas.
Check whether the classification (see "Marking" above and marking on the unit) is suitable 
for the application.

Installation remarks / Installation

•  Adhere to the respective national regulations and provisions as well as the relevant 

installation regulations. 

•  Avoid electrostatic charging on plastic units and cables.
•  To avoid electrostatic charging clean the unit with a damp cloth only. Rubbing with non-

conductive materials must be strictly avoided.

•  To avoid electrostatic charging steps must be taken to ensure the equalisation of potential 

of metal parts (plug housing, fixing elements, protective housing, etc.).

•  Do not mount the unit in the dust flow.
•  Avoid dust deposits on the units.
•  Protect the units and the cables efficiently against damage.
•  For the connections and the electrical characteristics please see the unit marking or the 

technical data sheet.

•  Avoid direct radiation with high UV components (sunlight). Mount the unit in a protected 

place.

•  M12 plugs may only be opened or closed in a sufficiently clean environment.
•  The secure fit of the impact protection housing for the sensor must be checked depending 

on the installation conditions (temperature, vibration,...) and at intervals to be defined by 
the operator.