
23
US
9.4.2 Scaling of the analogue value for temperature
►
Select [SEL2] and set [TEMP]�
►
Select [OU2 ] and set the function:
-[I] = current signal proportional to temperature (4…20 mA);
-[U] = voltage signal proportional to temperature (0…10 V)�
►
Select [ASP] and set the value at which the minimum output value is
provided�
►
Select [AEP] and set the value at which the maximum output value is
provided�
9.5 User settings (optional)
9.5.1 Determine the standard unit of measurement for volumetric flow
►
Select [Uni] and set the unit of measurement: [GPm] or [GPH]�
The setting only has an effect on the volumetric flow value� The counter
values (consumed quantity) are automatically displayed in the unit of mea-
surement providing the highest accuracy�
9.5.2 Configuration of the standard display
►
Select [SELd] and determine the standard process category�
-[FLOW] = display shows the current volumetric flow value in the stan-
dard unit of measurement�
-[TOTL] = display indicates the current meter count in gal, 10
3
gal or
10
6
gal�
-[TEMP] = display indicates the current medium temperature in °F�
►
Select [diS] and determine the update rate and orientation of the display:
-[d1] = update of the measured values every 500 ms�
-[d2] = update of the measured values every 1000 ms�
-[d3] = update of the measured values every 2000 ms�
-[rd1], [rd2], [rd3] = display as for d1, d2, d3; rotated by 180°�
-[OFF] = the display is switched off in the operating mode�
9.5.3 Setting the output logic
►
Select [P-n] and set [PnP] or [nPn]�
9.5.4 Setting the start-up delay
►
Select [dSt] and set the numerical value in seconds�
9.5.5 Setting the damping of the measured values
►
Select [dAP] and the damping constant in seconds (t value 63 %)�