Base product data 

Â

A88 circuit breaker with electronic release of KARAT series of IEK 

trademark (hereinafter referred to as circuit breaker) is designed to conduct 
current in normal mode and turn off overcurrents in case of short circuits and 
overloads, as well as for infrequent (up to 30 times a day) operational switching 
on and off of electrical circuits in three-phase alternating current electrical 
networks with voltage up to 400 V and frequency of 50 Hz. 

The circuit breaker meets the requirements of Directive No. 2014/30/EU, 

2014/35/EU, IEC 60947-2.

The circuit breaker can be operated under the following conditions:
– operating temperature range from minus 25 

°

Ñ

 to plus 40 

°

Ñ

;

 

base altitude 

 no more than 1000 m, operation at the altitude of up to 

2000 m is allowed with a decrease of rated current up to 10 %;

– environment condition group according to IEC 60947-1 – A, B*;
– utilization category according to IEC 60947-2 – 

Â

 (can be used to ensure 

selectivity);

– maximum value of relative humidity – 90 % and at temperature plus 20 

°

Ñ

;

– no direct exposure to solar-radiation;
– non-explosive environment, not containing aggressive gases and vapors in 

concentrations that destroy metals and insulation, not saturated with conductive 
dust and water vapors.

The circuit breaker is intended for use in an environment with pollution 

degree 3 (conductive pollution is possible or dry, non-conductive pollution that 
becomes conductive due to expected condensation).

The circuit breaker is equipped with an electronic microprocessing release 

MP211, which provides overload protection with an inverse long tripping delay 
and an inverse time-current characteristic, and also provides short-circuit 
protection with adjustable tripping. MP211 parameters are shown in table 2.

Specifications

The technical parameters of the circuit breaker depending on the type are 

listed in table 1.

Degree of protection of the circuit breaker case is IP30, of terminals for 

connecting external conductors 

 IP00

.

ÂÀ

88 CIRCUIT BREAKERS WITH ELECTRONIC RELEASE 

EN

REAL ABILITY

When using the circuit breaker in a group B environment, special devices should be used to 

protect against unwanted electromagnetic interferences.

 

K

ARA

T

Summary of Contents for BA88-32

Page 1: ... Â âîçìîæíî èñïîëüçîâàíèå äëÿ îáåñïå åíèÿ ñåëåêòèâíîñòè Âûêëþ àòåëü ïðåäíàçíà åí äëÿ èñïîëüçîâàíèÿ â ñðåäå ñî ñòåïåíüþ çàãðÿçíåíèÿ 3 âîçìîæíû òîêîïðîâîäÿùèå çàãðÿçíåíèÿ èëè ñóõèå íå òîêîïðîâîäÿùèå çàãðÿçíåíèÿ ñòàíîâÿùèåñÿ òîêîïðîâîäÿùèìè âñëåäñòâèå îæèäàåìîé êîíäåíñàöèè ìàêñèìàëüíîå çíà åíèå îòíîñèòåëüíîé âëàæíîñòè 90 è òåìïå ðàòóðå ïëþñ 20 Ñ ãðóïïà óñëîâèÿ îêðóæàþùåé ñðåäû ïî ÃÎÑÒ IEC 60947 1 A B...

Page 2: ...ìåíäóåòñÿ èñïîëüçîâàòü âìåñòå ñ ãèáêèìè ïðîâîäíèêàìè íàêîíå íèêè ïåðåõîäíèêè â êîìïëåêò ïîñòàâêè ÂÀ88 35 íå âõîäÿò Ðàçìåðû ïðèñîåäèíÿåìûõ íàêîíå íèêîâ ïåðåõîäíèêîâ è øèí äîëæíû ñîîòâåòñòâîâàòü ïðåäñòàâëåííûì íà ðèñóíêå 5 èëè 6 Ðàçìåð îïðåññîâû âàåìîé îáæèìàåìîé ñ ïîìîùüþ íàêîíå íèêà æèëû ñëåäóåò ïîäáèðàòü ñ ó åòîì òðåáîâàíèé ÂÑÍ 13983 Òåõíè åñêèå õàðàêòåðèñòèêè âûêëþ àòåëÿ â çàâèñèìîñòè îò òèïîèñï...

Page 3: ... ðàáî åå ïîëîæåíèå âûêëþ àòåëÿ â ïðîñòðàíñòâå íà âåðòèêàëüíîé ïëîñêîñòè âûâîäàìè 1 3 5 ââåðõ äîïóñêàåòñÿ óñòàíîâêà íà âåðòèêàëüíîé ïëîñêîñòè ñ ïîâîðîòîì âûâîäîâ 1 3 5 âëåâî è âïðàâî íà 90 Òðåáóåòñÿ òîëüêî îäíà íàñòðîéêà äëÿ âñåõ ôàç ïðè ýòîì ñðàáàòûâàíèå ðàñöåïèòåëÿ ïðîèñõîäèò îäíîâðåìåííî äëÿ âñåõ ïîëþñîâ âûêëþ àòåëÿ Êîíòàêòíûå ñîåäèíåíèÿ âíåøíèõ ïðîâîäíèêîâ è âûâîäîâ âûêëþ àòåëÿ äîëæíû óäîâëåòâî...

Page 4: ...êå èçãîòîâèòåëÿ â ïîìåùåíèÿõ ñ åñòåñòâåííîé âåíòèëÿöèåé ïðè òåìïåðàòóðå îêðóæàþùåãî âîçäóõà îò ìèíóñ 25 C äî ïëþñ 40 C è îòíîñèòåëüíîé âëàæíîñòè äî 90 è òåìïåðàòóðå ïëþñ 20 C Ñðîê ñëóæáû è ãàðàíòèè ïðîèçâîäèòåëÿ Ãàðàíòèéíûé ñðîê ýêñïëóàòàöèè âûêëþ àòåëÿ 5 ëåò ñî äíÿ ïðîäàæè ïðè óñëîâèè ñîáëþäåíèÿ ïîòðåáèòåëåì ïðàâèë ìîíòàæà ýêñïëóàòàöèè òðàíñïîðòèðîâàíèÿ è õðàíåíèÿ Ïðåòåíçèè ïî âûêëþ àòåëþ íå ïðèí...

Page 5: ...ty 90 and at temperature plus 20 Ñ no direct exposure to solar radiation non explosive environment not containing aggressive gases and vapors in concentrations that destroy metals and insulation not saturated with conductive dust and water vapors The circuit breaker is intended for use in an environment with pollution degree 3 conductive pollution is possible or dry non conductive pollution that b...

Page 6: ...tric schematic diagram of circuit breaker is shown on the figure 3 The normal operating position of the circuit breaker in space is on a vertical plane with terminals 1 3 5 upwards installation on a vertical plane with the rotation of terminals 1 3 5 to the left or right by 90 is allowed The circuit breaker is a repairable product It is necessary periodically at least once a year to check the tigh...

Page 7: ... load current of at least 15 of the rated current even if there is voltage in only one phase The protection unit includes three current transformers a microprocessor module and a trip electromagnet that acts directly on the circuit breaker mechanism Current transformers installed inside the release housing provide power to the release electronic circuit and generate the signals that are necessary ...

Page 8: ...è êðåïåæíûõ ýëåìåíòîâ äëÿ ïðèñîåäèíåíèÿ âíåøíèõ ïðîâîäíèêîâ ÍЧì Tightening torque of fasteners for connecting external conductors NЧm 12 1 5 ñ ïîìîùüþ êëþ à using a wrench ñ ïîìîùüþ êëþ à using 30 1 5 a wrench 10 0 5 ñ ïîìîùüþ êëþ à using a wrench 30 1 5 a wrench ñ ïîìîùüþ êëþ à using Ðàçìåð ðåçüáû êðåïåæíûõ ýëåìåíòîâ äëÿ ïðèñîåäèíåíèÿ âíåøíèõ ïðîâîäíèêîâ Thread size of fasteners for connecting ex...

Page 9: ... ÐÂ 250 ÐÂ 250 315 ÐÂ 400 ÐÂ 400 ÐÂ 800 ÐÂ 500 630 ÐÂ 1600 ÐÂ 1250 ÐÂ 1000 Âõîäÿò â êîìïëåêòàöèþ âûêëþ àòåëÿ Supplied with circuit breaker Ñå åíèå æåñòêîãî îäíîæèëüíîãî èëè ìíîãîæèëüíîãî 2 ïðîâîäíèêà ìì Cross section of a rigid solid or stranded 2 conductor mm Ñå åíèå ãèáêîãî 2 ïðîâîäíèêà ìì Cross section of flexible conductor 2 mm Ñå åíèå ðàçìåðû ìì ìåäíîé øèíû 2 ìì Cross section dimensions mm of...

Page 10: ...88 43 1000 250 50ґ5 500 50ґ10 250 50ґ5 500 50ґ10 1250 250 50ґ5 500 50ґ10 250 50ґ5 500 50ґ10 1600 250 50ґ5 500 50ґ10 250 50ґ5 500 50ґ10 Â ñêîáêàõ óêàçàíî ñå åíèå àëþìèíèåâûõ ïðîâîäíèêîâ The cross section of aluminum conductors is indicated within the brackets íàèìåíüøåå minimal íàèìåíüøåå minimal íàèìåíüøåå minimal íàèìåíüøåå minimal íàèáîëüøåå maximal íàèáîëüøåå maximal íàèáîëüøåå maximal íàèáîëüø...

Page 11: ...175 200 225 237 5 250 ÂÀ88 37 400 160 200 240 280 320 360 380 400 ÂÀ88 40 800 320 400 480 560 640 720 760 800 ÂÀ88 43 1000 400 500 600 700 800 900 950 1000 ÂÀ88 43 1250 500 625 750 875 1000 1125 1187 5 1250 ÂÀ88 43 1600 640 800 960 1120 1280 1440 1520 1600 Òèï Type I À n I À m 1 5 2 4 6 8 10 12 ÂÀ88 35 250 375 500 1000 1500 2000 2500 3000 ÂÀ88 37 400 600 800 1600 2400 3200 4000 4800 ÂÀ88 40 800 12...

Page 12: ...g in withdrawable design 3 áîêîâûå ýëåìåíòû äëÿ âûäâèæíîãî èñïîëíåíèÿ side elements for withdrawable design 4 ìåæôàçíûå ïåðåãîðîäêè interphase barriers 5 âòû íûå êîíòàêòû plug in contacts 6 êëåììíûå êðûøêè terminal covers 7 íàêëàäíàÿ êðûøêà êîðïóñà detachable cover of case 8 ëèöåâàÿ ïàíåëü âûêëþ àòåëÿ circuit breaker front panel 9 10 áîêîâûå çàãëóøêè âûêëþ àòåëÿ circuit breaker side plugs 16 ðàñøè...

Page 13: ...ðàêòåðèñòèêè âûêëþ àòåëåé ñ ýëåêòðîííûì ðàñöåïèòåëåì Figure 2 Time current characteristics of circuit breakers with electronic release ÌÐ211 Ðèñóíîê 3 Ýëåêòðè åñêàÿ ñõåìà âûêëþ àòåëÿ Figure 3 Electrical schematic of circuit breaker 1 2 3 4 5 6 Ò1 Ò2 Ò3 ...

Page 14: ...àçìåðû âûêëþ àòåëÿ Figure 4 Overall and mounting dimensions of circuit breaker Ðàçìåðû Dimensions mm ÂÀ88 35 ÂÀ88 37 ÂÀ88 40 ÂÀ88 43 À 35 44 70 70 À1 35 44 70 70 À2 181 214 237 378 À3 90 5 105 110 203 Â 105 140 210 210 Â1 105 105 140 140 Í 218 254 268 420 Í1 109 125 125 224 Í2 105 105 105 105 L 135 135 167 5 222 L1 113 113 117 146 5 L2 101 5 101 5 101 5 138 5 ЖD 4 îòâ holes Ж5 5 Ì5 4 îòâ holes Ж5 ...

Page 15: ...èê ïåðåõîäíèê äëÿ adapter lugs for ÂÀ88 35 â íàêîíå íèê ïåðåõîäíèê äëÿ adapter lugs for ÂÀ88 40 ã íàêîíå íèê ïåðåõîäíèê äëÿ adapter lugs for ÂÀ88 43 á íàêîíå íèê ïåðåõîäíèê äëÿ adapter lugs for ÂÀ88 37 Íîìèíàëüíîé òîê Rated current of ÂA 35 À Í mm 63 80 100 125 160 200 4 250 5 Íîìèíàëüíîé òîê Rated current of ÂA 40 À L1 mm S mm 400 20 7 500 20 7 630 22 8 800 24 9 24 33 44 53 Ж10 2 отв holes S 6 40...

Page 16: ...üíîé òîê Rated current of ÂA À Í mm 63 80 100 125 160 200 4 250 5 á ðàñøèðåííûå âûâîäû äëÿ extended outputs for ÂÀ88 37 Íîìèíàëüíîé òîê Rated current of ÂA À Í mm 250 5 315 400 6 20 30 53 13 33 10 19 40 Н Ж8 6 Ж10 1 53 33 0 125 10 20 Ж10 1 Ж8 6 Н 18 4 12 20 30 53 13 33 10 19 20 Н Ж8 6 Ж10 1 1 2 14 4 12 60 10 38 25 Ж12 1 25 Ø10 6 Н 1 2 14 4 12 60 38 25 Ж10 6 10 Н 1 2 14 4 38 12 60 10 25 Ø 1 2 1 35 ...

Page 17: ...s for ÂA88 43 Íîìèíàëüíîé òîê Rated current of ÂA À Í mm 400 5 500 630 6 800 8 50 80 12 6 47 5 12 22 22 50 50 Ж11 2 53 5 62 5 130 18 H 15 47 5 Ж12 6 53 5 62 5 130 18 H 50 80 12 6 47 5 12 22 22 50 50 Ж11 2 15 47 5 Ж12 6 50 47 5 80 50 47 5 12 22 22 Ж11 2 12 6 Ж12 6 15 53 5 62 5 130 18 H 2 отв hole 2 отв hole 2 отв hole 4 отв hole 4 отв hole 4 отв hole 4 отв hole 4 отв hole 4 отв hole 26 3 29 5 Н 70 ...

Page 18: ...òåëÿìè minimum distance between two circuit breakers vertically installed 1 íå èçîëðîâàííîå ïðèñîåäèíåíèå non insulated connection 3 êàáåëüíûå íàêîíå íèêè ñable lugs 2 èçîëèðîâàííûé êàáåëü insulated cable Òèï âûêëþ àòåëÿ Circuit breaker type Óñòàíîâêà â ìåòàëëè åñêîì çàçåìëåííîì ùèòå Installation in metal earthed switchboard Óñòàíîâêà â èçîëèðîâàííîì ùèòå Installation in an insulated switchboard Í...

Page 19: ...se á ïåðåêëþ àòåëü êðèâîé ñðàáàòûâàíèÿ çàùèòû îò ïåðåãðóçêè overload curve switch â ïåðåêëþ àòåëü óñòàâêè çàùèòû îò êîðîòêîãî çàìûêàíèÿ short circuit protection setting switch ã âðåìÿòîêîâàÿ êðèâàÿ time current curve à ïåðåêëþ àòåëü óñòàâêè çàùèòû îò ïåðåãðóçêè overload protection setting switch a á â ã ÌÐ211 tr I 6lr tr I 6lr Èçäàíèå Version 1 ...

Reviews: