Ðèñóíîê 6 – Ìèíèìàëüíûå ðàññòîÿíèÿ äëÿ óñòàíîâêè âûêëþ÷àòåëÿ / Figure 6 – Minimum distances
to install the switch
А
B
C
H
H
H
1
3
2
á) Ìèíèìàëüíûå ðàññòîÿíèÿ óñòàíîâêè
âûêëþ÷àòåëÿ â ùèòå / Minimum distance
of installation
â) Ìèíèìàëüíûå ðàññòîÿíèÿ ìåæäó äâóìÿ âåðòèêàëüíî
óñòàíîâëåííûìè âûêëþ÷àòåëÿìè
/ Minimum distance
between two circuit
of circuit breaker in the switchboard
1 – Íåèçîëèðîâàííîå ïðèñîåäèíåíèå /
Non insulated connection
2 – Èçîëèðîâàííûé êàáåëü /
Insulated cable
3 – Êàáåëüíûå íàêîíå÷íèêè /
Cable lugs
Òèïîèñïîëíåíèå /
Type
Óñòàíîâêà â ìåòàëëè÷åñêîì
çàçåìëåííîì ùèòå / Installation in a
metal grounded shield
Óñòàíîâêà â èçîëèðîâàí-íîì ùèòå
/ Installation in an isolated shield
Í, mm
D, mm
À, mm
Â, mm
Ñ, mm
À, mm
Â, mm
Ñ, mm
ÂÀ88-32
35
20
35
30
10
30
90
110
ÂÀ88-35
45
25
45
40
10
40
140
120
ÂÀ88-39
50
25
50
45
0
45
140
140
ÂÀ88-40
50
25
50
45
10
45
180
210
ÂÀ88-43
55
25
55
50
10
50
180
210