background image

 

10 

 

 iTDC Quick Installation Guide

 

 

Mar.11.2010 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

(

Figure: RS422 Multiple Connection

 

 
 

1  

Recommended Communication Cable

 

 

It is recommended to use STC(Shielded Twisted Pair) cable for RS422 communication.

   

2  

GND Connection

   

       

As the figure above, connect an end of Shield wire to the Power terminal block(GND) of iTDC/iTDC-SR. If you 
connect  both  ends  of  Shield  wire  to  the  Power  terminal  block(GND)  of  iTDC/iTDC-SR,  currents  may  flow 
because voltage levels of both sides are different then it causes communication error. Thus, must connect 

only one end of the Shield wire as the figure above.

   

3  

Termination Resistor Connection   

     

When  you  connect  RS232/RS422  Converter  and  iTDC/iTDC-SR,  connect  Termination  Resistor  to  the  start 
and  end  points  of  the  wire  as  the  figure  above.  If  the  length  of  communication  wire  is  too  long  in  one 

communication  loop,  it  causes  communication  problem  from  the  cracked data or  decrement.  To prevent  it, 
connect  Termination  Resistor  as  the  figure  above.  But,  don’t  use  Termination  Resistor  for  short-distance 
communication wire. If you use Termination Resistor in short-distance, it could cause communication errors.     

 

 

 

Caution 

Summary of Contents for iTDC EIO8

Page 1: ...Quick Installation Guide iTDC iTDC SR EIO88 MULTI DOORS ACCESS CONTROL SYSTEM...

Page 2: ...aders instead of No 8 Exit Buttons In this case connect each reader to reader port No 2 of iTDC iTDC SR reader port No 4 of iTDC iTDC SR Figure iTDC iTDC SR Installation Layout to Control 2 Doors No C...

Page 3: ...gure below is iTDC iTDC SR installation layout to control 3 doors Figure iTDC iTDC SR Installation Layout to Control 3 Doors No Code PC for installing application software STARWATCH iTDC PRO I II STAR...

Page 4: ...lation layout to control 4 doors Attach EIO88 Figure iTDC iTDC SR Installation Layout to Control 4 Doors No Code PC for installing application software STARWATCH iTDC PRO I II STARWATCH STANDARD iTDC...

Page 5: ...1 iTDC iTDC SR No Code Power Port Terminal Block RS422 Communication Port Terminal Block RS232 Communication Port Terminal Block TTL Output Port Terminal Block Relay Output Port Terminal Block Board I...

Page 6: ...6 iTDC Quick Installation Guide Mar 11 2010 1 2 1 EIO88 No Code Input Port Terminal Block 1 4 Output Port Terminal Block 5 8 Input Port Terminal Block 1 4 Output Port Terminal Block 5 8...

Page 7: ...of DIP switch has assigned address value and the Board ID is the sum value of each switch set to ON position Refer to the example below Figure Position of DIP Switch and Magnification of the Switch Ex...

Page 8: ...1ST class EARTH GROUND EARTH GROUND wiring equalizes all ground level to zero and protects the device from the thunderbolt or surge voltage Figure iTDC iTDC SR GND Wiring 3 2 iTDC iTDC SR POWER WIRING...

Page 9: ...unctions 2 Connection between RS422 RS232 Converter and iTDC iTDC SR First connect RS422 RS232 Converter to the first iTDC iTDC SR in cross connection as follows Connect RS422 TX Port of the Converter...

Page 10: ...rent then it causes communication error Thus must connect only one end of the Shield wire as the figure above 3 Termination Resistor Connection When you connect RS232 RS422 Converter and iTDC iTDC SR...

Page 11: ...Port of the first iTDC iTDC SR to RS422 RX Port of the second iTDC iTDC SR Connect RS422 RX Port of the first iTDC iTDC SR to RS422 TX Port of the second iTDC iTDC SR Connect RS422 RX Port of the firs...

Page 12: ...are different then it causes communication error Thus must connect only one end of the Shield wire as the figure above 3 Termination Resistor Connection When you connect RS232 RS422 Converter and iTD...

Page 13: ...gram to set network and check operation status is contained in Application software iTDC PRO I II STARWATCH STANDARD CD Install IIM100A Configuration Tool and then set TCP IP Module information for co...

Page 14: ...default 0 for Server IP Port Select Server Mode for Network Mode Refer to table below Column Name Setting Value Local IP The IP address assigned from corresponding network Not duplicated Gateway The...

Page 15: ...e and Char of selected TCP IP module Select 30000 for Inactivity Time 0 for Time 0 for Size 00 for Char Refer to table below Column Name Setting Value Inactivity Time 30000 Time 0 Size 0 Char 00 8 If...

Page 16: ...F reader to Reader Port terminal block D0 of iTDC iTDC SR Connect DATA1 white wire of RF reader to Reader Port terminal block D1 of iTDC iTDC SR Figure Reader Wiring You can use external 12V DC power...

Page 17: ...onnect Door Contact to Input Port terminal block INPUT_2 of iTDC iTDC SR Door 2 Connect Exit Button to Input Port terminal block INPUT_3 of iTDC iTDC SR Door 2 Connect Door Contact to Input Port termi...

Page 18: ...f you install input devices such as a reader and an exit button on the metal flame Earth GND should be connected to the metal frame If you don t connect Earth GND to metal frame static electricity fro...

Page 19: ...Must connect an anti inverse voltage diode between wire and wire of Door Lock IMPORTANT Figure Power Fail Safe Door Lock Wiring Connect an anti inverse voltage diode as shown above when wiring Door L...

Page 20: ...ck RNO1 of iTDC iTDC SR Connect wire of Door Lock to GND wire of DC12V power supply Must connect an anti inverse voltage diode between wire and wire of Door Lock IMPORTANT Figure Power Fail Secure Doo...

Page 21: ...or Power Fail Secure But separate power source must be applied and use external Relay in both Power Fail Secure and Power Fail Safe door lock Figure 24V Door Lock and Automatic Door Wiring If you don...

Page 22: ...ice IMPORTANT Figure Alarm Wiring Connect an anti inverse voltage diode as shown above when wiring Door Lock or Alarm If you don t an anti inverse voltage diode external noise flows in then it causes...

Page 23: ...or Entrance Exit Reader Exit Button Normal Output Alarm Output 3 Door Attach EIO88 Door 1 Entrance Reader 1 iTDC Relay 1 iTDC Relay 2 Exit Reader 2 iTDC Input 1 iTDC Relay 1 iTDC Relay 2 Door 2 Entran...

Page 24: ...alization switches and then keep it for more than 2 seconds then beep sound will be generated Once beep sound is generated release the switches then initialization process is starting After initializa...