INSTALLATION TIPS & CHECK POINTS
p.20
2
RECOMMENDED CABLE TYPE AND PERMISSIBLE LEN
GTH OF CABLE
Reference
Description
Cable specification
Maximum distance
1
DC +12V → Power iMDC-MAIN
DC +12V → Power iMDC-RIM
Belden #9409, 18 AWG
2 conductor, unshielded
3m
Reader (Power and Data)
Reader → iMDC-RIM
Belden #9512, 22 AWG
4 conductor, shielded
150m
Belden #9514, 22 AWG
8 conductor, shielded
3
Door Contact
Exit Button
Sensor Input
Input → iMDC-RIM
Belden #9512, 22 AWG
4 conductor, shielded
300m
Belden #9514, 22 AWG
8 conductor, shielded
4
Door Lock, Alarm Device
Lock (Alarm) → iMDC-RIM
Belden #9409, 18AWG
2 conductor, unshielded
300m
5
iMDC Cable
iMDC-RIM Cable
iMDC-MAIN ↔ iMDC-MAIN
iMDC-MAIN ↔ iMDC-RIM
iMDC-MAIN ↔ Host P.C
UTP Cable CAT5(Catagory5)
100m
~
150m
3
CHECK POINT DURING INSTALLATION
3.1
REVERSE DIODE CONNECTION
If you connect an inductor (Door Locks or Alarm device) to the output relays, there will be a
high surge voltage created while the inductor is turning on and off. To protect this problem,
connect the reverse diode as the figure below.
1 You need thicker wire if you connect the reader with high current consumption
Summary of Contents for iMDC-MAIN
Page 1: ......
Page 2: ......
Page 6: ......
Page 10: ......
Page 18: ...iMDC INSTRUCTION p 12 3 DIMENSION 4 iMDC MAIN BOARD ...
Page 28: ......
Page 42: ......
Page 52: ......
Page 62: ......
Page 72: ......
Page 75: ...p 69 DIODE SPECIFICATION 3 DIODE SPECIFICATION Model 1N4007 Power Current 50 1000 V Min 1 0 A ...
Page 76: ......
Page 78: ......