(C) IDM ENERGIESYSTEME GMBH
3. Technical data Hygienik 2.0
Installation instructions Hygienik 2.0
10
Technical data
Te
chnical d
a
ta
Hygienik 2.0
Unit
2000
4)
/25
2000
4)
/35
2000
4)
/50
2000
4)
/70
Energy e
ffi
ciency class
-
n.a
1
n.a
1
n.a
1
n.a
1
Average power loss
W
164
164
164
164
Total storage tank contents
l
2000
2000
2000
2000
Storage tank contents above LSP
2)
l
700
700
700
700
Storage tank contents below LSP
l
1300
1300
1300
1300
Diameter incl. insulation
mm
1340
1340
1340
1340
Height incl. insulation
mm
2505
2505
2505
2505
Installation depth without insulation
mm
Ø 1100
Ø 1100
Ø 1100
Ø 1100
Tilted dimension of tank body
mm
2440
2440
2440
2440
Weight storage tank without LSP
6
kg
206/258
7
206/258
7
206/258
7
206/258
7
Weight storage tank with LSP
6
kg
220
220
220
220
Single tapping volume at 45°C without LSP
2
l
2100
2100
2100
2100
Single tapping volume at 45°C with LSP
2
l
734
734
734
734
Tapping output
l/min
25
35
50
70
Max. res. units without LSP**
-
7
11
18
30
Max. res. units with LSP**
-
7
8
8
8
Max. hotel rooms with LSP**
-
4
7
11
19
Max. showers at sport facilities
-
6
8
12
17
1
In accordance with EU Ordinance 812/2013 on the energy labeling of hot water
storage tanks, there is no energy labeling
for hot water storage tanks with a total volume exceeding 500 l
2
Calculated with:
Tapping temperature 45°C
Cold water temperature 15°C
Storage temperature 60°C
Storage return temperature 25°C
Storage- and mixing loss 10%
3
For a one-time storage tank charge calculated with:
Tapping temperature 45°C
Cold water temperature 10°C
Storage temperature 55°C
Storage return temperature 25°C
4
For a one-time storage tank charge calculated with:
Tapping temperature 45°C
Cold water temperature 10°C
Storage temperature 55°C
Storage return temperature 25°C
5
Hygienik 2000 l - 2.0 is also available with fl ange connection
as Hygienik 2000 Max 2.0
6
Weight specifi cation without Insulation and hot water station
7
Weight storage tank Hygienik 2000 Max 2.0