background image

812556_Rev

.13 - Original Instructions

THE 

ENERGY

FAMILY

Te c h n i c a l   d o c u m e n t a t i o n

I n s t a l l a t i o n   i n s t r u c t i o n

SINCE

QUALITY

HEAT PUMPS FROM AUSTRIA 

www.idm-energie.at

H Y G I E N I K   2 . 0

W I T H   H O T   WAT E R   S TAT I O N   2 . 0

Summary of Contents for HYGIENIK 2.0

Page 1: ...812556_Rev 13 Original Instructions THE ENERGYFAMILY Technical documentation Installation instruction SINCE QUALITY HEAT PUMPS FROM AUSTRIA www idm energie at HYGIENIK 2 0 WITH HOT WATER STATION 2 0...

Page 2: ...3 Notes on dimensioning 7 3 TECHNICAL DATA HYGIENIK 2 0 8 4 INSTALLATION 20 4 1 Installation conditions for the Hygienik 2 0 20 4 2 Installation location of the Hygienik 2 0 20 4 3 Connecting sockets...

Page 3: ...L Hygienik 2 0 Termo 1 HC Passive cooling S2 2 0 2 5 1 0 41 6 2 5 AERO ALM Hygienik 2 0 with separatin plate circulation L7 1 0 1 0 1 42 6 2 6 AERO ALM Solar 12 m2 Hyginik 2 0 with separating plate 1...

Page 4: ...t of the tank means an increased risk of accidents 1 4 Servicing and maintenance Regular maintenance as well as an inspection and servicing of all important system components ensure safe and economica...

Page 5: ...of the local authorities Disposal contrary to the regulations may lead to damage to the environment and health and may be subject to penalty under law 1 10 Quality of the service water We recommend t...

Page 6: ...layer separate plate main tains temperature stratification in particular when using the Hygienik 2 0 with an iDM heat pump Without layer separate plate only for hot water heating The Hygienik 825 wit...

Page 7: ...family houses with solar system for hot water and heating support 825 liter without sepa ration plate for two to four family houses for hot water heating only 1000 liter with sepa ration plate for on...

Page 8: ...018 1018 Height incl insulation mm 1890 1890 1970 1970 2170 2170 Installation depth without insulation mm 650 650 790 790 790 790 Tilted dimension of tank body mm 1800 1800 1910 1910 2080 2080 Weight...

Page 9: ...70 1170 1170 Height incl insulation mm 2170 2400 2400 2400 2400 Installation depth without insulation mm 790 950 950 950 950 Tilted dimension of tank body mm 2080 2320 2320 2320 2320 Weight storage ta...

Page 10: ...734 734 734 734 Tapping output l min 25 35 50 70 Max res units without LSP 7 11 18 30 Max res units with LSP 7 8 8 8 Max hotel rooms with LSP 4 7 11 19 Max showers at sport facilities 6 8 12 17 1 In...

Page 11: ...at 45 C Si multaneity factor in acc with Handbuch f r Heizung L ftung Klima Recknagl Sprenger Corresponds to the average tapping profile of a family according to EN 15450 2008 or the load profile M a...

Page 12: ...data Technical data Hygienik 500 2 0 with without layer separate plate Item Connection Dimen sion 1 Flow hot water station R 1 2 Return hot water station R 1 3 Socket for electric heating immerser R...

Page 13: ...al data Item Connection Dimension 1 Flow hot water station R 1 2 Return hot water station R 1 3 Socket for electric heating immerser R 2 4 Socket for circulation lance or return circulation station R...

Page 14: ...9 Flow HGL resp domestic hot water or flow circulation station R 1 10 Flow heat pump R 1 11 Flow second heat generator R 1 12 Optional return R 13 Return heating R 14 Return heat pump R 15 Sensor ter...

Page 15: ...ical data Item Connection Dimension 1 Flow hot water station R 1 2 Return hot water station R 1 3 Socket for electric heating immerser R 2 4 Socket for circulation lance or return circulation station...

Page 16: ...n be installed on the top of the bu er tank Front view Rear view Item Connection Dimension 1 Flow hot water station R 1 2 Return hot water station R 1 3 Socket for electric heating immerser R 2 4 Sock...

Page 17: ...n R 1 5 Flow HGL resp domestic hot water R 1 2 6 Flow heat pump R 2 7 Return heat pump R 2 Hygienik 2000 2 0 with without layer separate plate Item Connection Dimension 8 Flow second heat generator So...

Page 18: ...iew Item Connection Dimension 1 Flange 4x DN100 PN6 2 Warm water station flow R 1 1 4 3 Warm water station return R 1 1 4 4 Electric heating immerser 2x R 2 5 Circulation 2x 2 6 Sleeve R 2 1 2 7 Venti...

Page 19: ...C IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2 0 19 Technical data Technical data Notes...

Page 20: ...f the installation room 4 3 Connecting sockets of the Hygienik 2 0 In order to avoid heat losses openings are not pro vided for all sockets in the insulation jacket Additional connections can be used...

Page 21: ...ip Once the insulation of the base has been attached the sensors must be fixed in position as shown on the equipment identification sticker on the tank body using the sensor terminal block The insulat...

Page 22: ...strip is hooked into the first catch and closed on the opposite side from bottom to top The insulation jacket is tightened using the hook strips until it lies snugly against the tank body When the ins...

Page 23: ...is necessary to ensure that the two upper and lower parts of the insulation are hung on the last catch of the hook strip so that the insula tion firmly encloses the storage body If the insulating par...

Page 24: ...otos on the left side of this page The plastic cover must not be mounted over the insulating jacket The wave at the upper end of the insulating jacket is a design feature and must not be covered by th...

Page 25: ...C IDM ENERGIESYSTEME GMBH Installation instructions Hygienik 2 0 25 Installation Installation Notes...

Page 26: ...enik 2 0 with a capacity of 1500 l and 2000 l The 50 l and 70 l hot water stations can also be mounted on a wall Optional accessories Controller UVR 67 Heat meter for 25 l min and 35 l min Heat meter...

Page 27: ...fittings The hot water station is connected at sockets 1 and 2 using the corrugated hoses Mounts as shown above are provided for installation of the hot water stations The holder for the hot water st...

Page 28: ...additional retaining screw Working from the front slide the iDM cover hood onto the hot water station in straight position until it snaps into place In order to avoid energy losses the cover hood sho...

Page 29: ...ery of the 50 l and 70 l hot water stations It is essential to fit these valves on the construction site if the hot water stations is to be mounted on the wall and not on the Hygienik 2 0 Ball valves...

Page 30: ...r the hot water stations 25ltr and 35ltr an optional circulation module Part no 173500 can be mounted Circulation pipe Remove plug Connect circulation pipe The circulation pipe is passed under the ret...

Page 31: ...lation pump on the circulation pipe and fix it in the holder by the ball valve When mounting the circulation pump it is essential to pay attention to the direction of flow Ball valve Circulation pump...

Page 32: ...eter can be installed with the 25l and 35l hot water stations Remove the brass pipe from the tank return and insert the metering unit of the heat meter The temperature sensor of the heat meter is inst...

Page 33: ...er station as shown in the photo above The shown corrugated hose is included in the scope of delivery of the heat quantity meter The sensor of the heat meter is installed in the flow of the hot water...

Page 34: ...ler The scope of delivery includes 2 brackets one for the 25l and 35l hot water stations and one for the 50l and 70l hot water stations Attach the bracket for the controller using the bore holes provi...

Page 35: ...a the installed flushing valves Connecting the hot water station electrically Electrical connection must be performed as shown in the enclosed electric circuit diagram 1 2 3 4 5 6 2 Hot water circulat...

Page 36: ...on gurations They are schematic diagrams and do not show the full range of components required When actually designing a system the speci c con ditions applicable standards and laws and the data and i...

Page 37: ...circuit S4 2 0 2 0 0 6 2 1 TERRA SW Complete Hygienik 2 0 3 heating circuits S4 1 0 1 0 0 6 2 2 TERRA SW Complete HGL Hygienik 2 0 with LSP and circulation S4 2 0 1 0 1 6 2 3 TERRA SWM HGL Hygienik 2...

Page 38: ...aces no professional planning of an executing companie On part of IDM Energiesysteme can no warrenty be taken concerning the function of the whole system General instructions for IDM system schemes mu...

Page 39: ...s is only a tentative suggestion for installing an IDM heat pump in the heating system This suggestion replaces no professional planning of an executing companie On part of IDM Energiesysteme can no w...

Page 40: ...uit Note This is only a tentative suggestion for installing an IDM heat pump in the heating system This suggestion replaces no professional planning of an executing companie On part of IDM Energiesyst...

Page 41: ...lve Groundwater circuit SHE Note This is only a tentative suggestion for installing an IDM heat pump in the heating system This suggestion replaces no professional planning of an executing companie On...

Page 42: ...be taken concerning the function of the whole system General instructions for iDM system schemes must be noted Throttle valve Hygienik 2 0 with separating plate Hydraulic module indoor unit AERO ALM...

Page 43: ...olar up to 12 m Hygienik 825 with SP und Solarexchanger 1 HC Hygienik 2 0 with SP and solar exchanger Hydraulic module indoor unit Solar up to 12 m piping with heating water The shut off valve between...

Page 44: ...M B42 TERRA AL Max HW CW RE A HC A FS TERMO Note This is only a tentative suggestion for installing an IDM heat pump in the heating system This suggestion replaces no professional planning of an execu...

Page 45: ...we recommend that after lling the system as the last step of commissioning you heat the tank content By setting the maximum boiler output for example the chimney sweep function and maximum ow tempera...

Page 46: ...matic air vent does not work If an automatic air vent is desired it can be mounted on top of the bu er If it is not possible to tap warm drinking water although the temperature in the Hy gienik 2 0 is...

Page 47: ...GV ZHUH DSSOLHG DFFRUGLQJO 1 1 1 1 9DOLG IRU WKH IROORZLQJ SURGXFWV RW ZDWHU VWDWLRQ RW ZDWHU VWDWLRQ IRU O PLQ GHOLYHU YROXPH RW ZDWHU VWDWLRQ IRU O PLQ GHOLYHU YROXPH RW ZDWHU VWDWLRQ IRU O PLQ GHOL...

Page 48: ...SITE SERVICE Our service technicians are happy to help on site Contact details for your regional customer service centre can be found on our website iDM Academy PRACTICAL KNOWLEDGE FOR SALES AND TECHN...

Reviews: