(6) Status
The analog status shows the status of the analog input or analog output for each channel. If the status is 0, this means the
value is normal as an analog value.
Analog input
Analog output
Status
Description
Analog Input Value
0
Operating normally
Current analog input value
1
Converting data (occurs for approximately 500 ms after the power is turned on and after the
program is downloaded)
Undefined
2
Initializing
0
3 to 4
Reserved
―
5
Wiring fault (out of maximum range)
Upper limit value
Signal type
Voltage
0 to 10 V
For V100
: 10.0 V or higher
For V201
and later: 10.2 V or higher
Current
4 to 20 mA
For V100
: 20.0 mA or higher
For V201
and later: 20.32 mA or higher
0 to 20 mA
For V100
: 20.0 mA or higher
For V201
and later: 20.4 mA or higher
Thermocouple/
resistance thermometer
Upper limit value or higher
6
Wiring fault (out of minimum range, open current loop)
Lower limit value
Signal type
Voltage
0 to 10 V
For V100
: 0 V or lower
For V201
and later: -0.2 V or lower
Current
4 to 20 mA
For V100
: 4.0 mA or lower
For V201
and later: 3.68 mA or lower
0 to 20 mA
For V100
: 0 mA or lower
For V201
and later: -0 mA or lower
Thermocouple/
resistance thermometer
Lower limit value or higher
7
Reserved (analog cartridge correction value error)
―
8
There is a difference in the configured content for the installed analog cartridge and the user
program
Undefined
9
The analog cartridge has not been installed
Undefined
10
The analog cartridge has been installed, but the type has been set to unused
Undefined
11 to 65,535 Reserved
―
*1 The analog cartridge version number is printed on the side of the analog cartridge. For details, see "Checking the Version Number" on page
Status
Description
Analog Output Signal
0
Operating normally
Current analog output value
1
Reserved
―
2
Initializing
0 V / 4 mA
3
Parameter setting error
Analog output value immediately before the error occurred
4 to 7
Reserved
―
8
There is a difference in the configured content for the installed
analog cartridge and the user program
0 V / 4 mA
9
The analog cartridge has not been installed
―
10
The analog cartridge has been installed, but the type has been set
to unused
0 V / 4 mA
11 to 65,535 Reserved
―
Summary of Contents for FC6A series
Page 1: ...B 1722 2 FC6A SERIES All in One Type User s Manual ...
Page 10: ...TABLE OF CONTENTS Preface 9 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 28: ...1 GENERAL INFORMATION 1 18 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 286: ...6 DEVICES 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 334: ...7 HMI FUNCTION 7 48 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 340: ...8 INSTRUCTIONS REFERENCE 8 6 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 360: ...9 FUNCTIONAL MODULES 9 20 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 368: ...10 ANALOG CARTRIDGE 10 8 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...