7: D
EVICE
A
DDRESSES
7-2
S
MART
AXIS P
RO
/ L
ITE
U
SER
'
S
M
ANUAL
FT9Y-B1378
Special Internal Relays
Special internal relays M8000 through M8177 are used for controlling the CPU operation and communication, and for indicating the
CPU statuses. All special internal relays cannot be used as destinations of advanced instructions.
Internal relays M300 through M335 are used to read input device statuses of the IOREF (I/O refresh) instruction.
Note:
Do not change the status of reserved special internal relays, otherwise the SmartAXIS may not operate correctly.
Special Internal Relay Device Addresses
Device
Address
Description
CPU
Stopped
Power
OFF
Read/
Write
Ladder
FBD
M8000
Start Control
Maintained
Maintained
Write
X
X
M8001
1-sec Clock Reset
Cleared
Cleared
Write
X
X
M8002
All Outputs OFF
Cleared
Cleared
Write
X
X
M8003
Carry (Cy) or Borrow (Bw)
Cleared
Cleared
Read
X
―
M8004
User Program Execution Error
Cleared
Cleared
Read
X
X
M8005
Remote I/O Slave 1 Communication Error
Operating
Cleared
Read
X
X
M8006
Remote I/O Slave 2 Communication Error
Operating
Cleared
Read
X
X
M8007
Remote I/O Slave 3 Communication Error
Operating
Cleared
Read
X
X
M8010
In daylight saving time period (system version 1.10 or later)
Operating
Cleared
Read
X
X
M8011-
M8012
— Reserved —
―
―
―
―
―
M8013
Calendar/Clock Data Write/Adjust Error Flag
Operating
Cleared
Read
X
X
M8014
Calendar/Clock Data Read Error Flag
Operating
Cleared
Read
X
X
M8015
— Reserved —
―
―
―
―
―
M8016
Calendar Data Write Flag
Operating
Cleared
Write
X
X
M8017
Clock Data Write Flag
Operating
Cleared
Write
X
X
M8020
Calendar/Clock Data Write Flag
Operating
Cleared
Write
X
X
M8021
Clock Data Adjust Flag
Operating
Cleared
Write
X
X
M8022
User Communication Receive Instruction Cancel Flag (Port 2)
Cleared
Cleared
Write
X
―
M8023
User Communication Receive Instruction Cancel Flag (Port 3)
Cleared
Cleared
Write
X
―
M8024
BMOV/WSFT Executing Flag
Maintained
Maintained
Read
X
―
M8025
Maintain Outputs While CPU Stopped
Maintained
Cleared
Read/Write
X
X
M8026
SD Memory Card Status
Maintained
Cleared
Read
X
X
M8027
SD Memory Card Writing Flag
Maintained
Cleared
Read
X
X
M8030
High-speed Counter (Group 1/I0)
Comparison Output Reset
Cleared
Cleared
Read/Write
X
M8031
Gate Input
Maintained
Cleared
Read/Write
X
M8032
Reset Input
Maintained
Cleared
Read/Write
X
M8033
Reset Status
Maintained
Cleared
Read
X
X
M8034
Comparison ON Status
Maintained
Cleared
Read
X
X
M8035
Overflow
Maintained
Cleared
Read
X
X
M8036
Underflow
Maintained
Cleared
Read
X
X
M8037
Count Direction
Maintained
Cleared
Read
X
X
M8040
High-speed Counter (Group 2/I2)
Comparison Output Reset
Cleared
Cleared
Read/Write
X
M8041
Gate Input
Maintained
Cleared
Read/Write
X
M8042
Reset Input
Maintained
Cleared
Read/Write
X
M8043
Comparison ON Status
Maintained
Cleared
Read
X
X
M8044
Overflow
Maintained
Cleared
Read
X
X
M8045
High-speed Counter (Group 3/I3)
Comparison Output Reset
Cleared
Cleared
Read/Write
X
M8046
Gate Input
Maintained
Cleared
Read/Write
X
M8047
Reset Input
Maintained
Cleared
Read/Write
X
M8050
Reset Status
Maintained
Cleared
Read
X
X
M8051
Comparison ON Status
Maintained
Cleared
Read
X
X
M8052
Overflow
Maintained
Cleared
Read
X
X
M8053
Underflow
Maintained
Cleared
Read
X
X
M8054
Count Direction
Maintained
Cleared
Read
X
X
Summary of Contents for SmartAXIS FT9Z-1A01
Page 1: ...FT9Y B1378 7...
Page 10: ...TABLE OF CONTENTS Preface 9 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 212: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 230: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 344: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 386: ...APPENDIX Appendix 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 Japanese Font JIS X0201...
Page 393: ......