CPU Module selection table
5
Selection table for changing from the FC4A/5A series Slim type -> the FC6A Plus
FC4A/5A
series No.
Main specifications
Recommended
FC6A series No.
for replacement
Main specifications
Power
supply
voltage
Program
capacity
(steps)
I/O specifications
Processing
speed
basic
command
(ns)
Number of
expandable
units
Max.
I/Os
Width
mm
Power
supply
voltage
Program
capacity
(steps)
I/O specifications
Processing
speed basic
command
(ns)
Number of
expandable
units
*1
Max.
I/Os
Width
mm
FC4A
-D20K3
24
VDC
27KB
(4.5K)
12 pts. input and
8 pts. output
transistor sink
(0.3A)
8 pts.:COM
1000
7
128 35.4
FC6A-
D16K1CEE
24
VDC
800KB
(100K)
8 pts. input and
8 pts. output
transistor sink
(0.5A)
8 pts.:COM
21
7
(15)
*2
(63)
*3
224
(
480
)
*2
(2016)
*3
70
FC4A
-D20S3
12 pts. input and
8 pts. output
transistor source
(0.3A)
8 pts.:COM
FC6A-
D16P1CEE
8 pts. input and
8 pts. output
transistor source
(0.5A)
8 pts.:COM
FC4A
-D20RK3
31.2KB
(5.2K)
12 pts. input and
6 pts. output
relay (2A)
3 pts.:COM1
2 pts.:COM2
1 pts.:COM3
2 pts. output
transistor sink
(0.3A)
2 pts.:COM0
224
47.5
FC6A-
D32K3CEE
16 pts. input and
16 pts. output
transistor sink
(0.1A)
16 pts.:COM
FC4A
-D20RS3
12 pts. input and
6 pts. output
relay (2A)
3 pts.:COM1
2 pts.:COM2
1 pts.:COM3
2 pts. output
transistor source
(0.3A)
2 pts.:COM0
FC6A-
D32P3CEE
16 pts. input and
16 pts. output
transistor source
(0.1A)
16 pts.:COM
FC4A
-D40K3
24 pts. input and
16 pts. output
transistor sink
(0.3A)
8 pts.:COM0
8 pts.:COM1
224
47.5
FC6A-
D32K3CEE
16 pts. input and
16 pts. output
transistor sink
(0.1A)
10 pts.:COM
FC4A
-D40S3
24 pts. input and
16 pts. output
transistor source
(0.3A)
8 pts.:COM0
8 pts.:COM11
FC6A-
D32P3CEE
16 pts. input and
16 pts. output
transistor source
(0.1A)
16 pts.:COM
*1
The number of expansible modules does not include expansion interface modules.
*2 The numbers in parentheses indicate the number of expansible modules and number of I/O
points when the FC5A series is combined with the expansion interface module (unibody type)
FC6A-EXM2 series.
*3 The numbers in parentheses indicate the number of expansible modules and number of I/O
points when the expansion interface module (unibody type) FC6A-EXM2 series and the
expansion interface module (separate type master) FC6A-EXM1M series are combined with the
expansion interface module (separate type slave) FC6A-EXM1S series.