MICRO/I Hardware Manual
2-15
2 Analog I/O Modules
2
Ex
pa
ns
io
n M
od
ule
s
■
Signal Type
The signal type that can be set differs according to the analog I/O module model. Select the analog I/O module that
corresponds to the user application and set the signal type. The signal type is the type of analog input to measure.
There are 24 signal types for the analog inputs, which are detailed as follows.
YES: Supported, NO: Not supported
Signal Type
FC6A-
J2C1
FC6A-
J2C4
FC6A-
J4A1
FC6A-
J4A4
FC6A-
J8A1
FC6A-
J8A4
FC6A-
J4CN1
FC6A-
J4CN4
FC6A-
J4CH1Y
FC6A-
J4CH4Y
FC6A-
J8CU1
FC6A-
J8CU4
FC6A-
L06A1
FC6A-
L06A4
FC6A-
L03CN1
FC6A-
L03CN4
Unused
YES
YES
YES
YES
YES
YES
YES
YES
0 to 10V DC
YES
YES
YES
YES
NO
NO
YES
YES
-10 to +10V DC
YES
YES
YES
YES
NO
NO
YES
YES
0 to 20mA DC
YES
YES
YES
YES
NO
NO
YES
YES
4 to 20mA DC
YES
YES
YES
YES
NO
NO
YES
YES
Type K
thermocouple
NO
NO
NO
YES
YES
YES
NO
YES
Type J
thermocouple
NO
NO
NO
YES
YES
YES
NO
YES
Type R
thermocouple
NO
NO
NO
YES
YES
YES
NO
YES
Type S
thermocouple
NO
NO
NO
YES
YES
YES
NO
YES
Type B
thermocouple
NO
NO
NO
YES
YES
YES
NO
YES
Type E
thermocouple
NO
NO
NO
YES
YES
YES
NO
YES
Type T
thermocouple
NO
NO
NO
YES
YES
YES
NO
YES
Type N
thermocouple
NO
NO
NO
YES
YES
YES
NO
YES
Type C
thermocouple
NO
NO
NO
YES
YES
YES
NO
YES
Pt100
NO
NO
NO
YES
NO
NO
NO
YES
Pt1000
NO
NO
NO
YES
NO
NO
NO
YES
Ni100
NO
NO
NO
YES
NO
NO
NO
YES
Ni1000
NO
NO
NO
YES
NO
NO
NO
YES
NTC Thermistor
NO
NO
NO
NO
NO
YES
NO
NO
PTC Thermistor
NO
NO
NO
NO
NO
YES
NO
NO
PTC Thermistor
(threshold)
NO
NO
NO
NO
NO
YES
NO
NO
Ohm meter
NO
NO
NO
NO
NO
YES
NO
NO
Expansion 0 to
20mA DC
NO
NO
YES
NO
NO
NO
NO
NO
Expansion 4 to
20mA DC
NO
NO
YES
NO
NO
NO
NO
NO
*1 Channels that are set to unused are not scanned.
The circuit is setup the same as when
0 to 10V DC
is selected as
Signal Type
.
0 is always stored in the analog data storage data registers for channels that are set to unused.
*2 For details, refer to “ PTC Thermistor (Threshold)” on page 2-22.