Introduction
This chapter describes general information about the Actuator-Sensor-Interface, abbreviated AS-Interface, and detailed
information about using the AS-Interface master module.
About AS-Interface
AS-Interface is a type of field bus that is primarily intended to be used to control sensors and actuators. AS-Interface is a
network system that is compatible with the IEC62026 standard and is not proprietary to any one manufacturer. A master
device can communicate with slave devices such as sensors, actuators, and remote I/Os, using digital and analog signals
transmitted over the AS-Interface bus.
The AS-Interface system is comprised of the following three major components:
•
One master, such as the
MicroSmart
AS-Interface master module (FC4A-AS62M)
•
One or more slave devices, such as sensors, actuators, switches, and indicators
•
Dedicated 30V DC AS-Interface power supply (26.5 to 31.6V DC)
These components are connected using a two-core cable for both data transmission and AS-Interface power supply. AS-
Interface employs a simple yet efficient wiring system and features automatic slave address assignment function, while
installation and maintenance are also very easy.
Applicable Sensors and Actuators for AS-Interface
AS-Interface Compatible Sensors and Actuators
AS-Interface compatible sensors and actuators communicate using the built-in AS-Interface function, and serve as AS-
Interface slaves when connected directly to the AS-Interface bus via a branch unit or a T-junction unit.
Sensors/Actuators Not Compatible with AS-Interface
Conventional sensors and actuators that are not compatible with the AS-Interface can also be connected to the AS-Inter-
face bus using a remote I/O slave and be handled in the same way as devices that are compatible with the AS-Interface.
Remote I/O Type Slave
Branch Unit
T-junction Unit
AS-Interface Non-compatible
Sensors/Actuators
AS-Interface Compatible Sensors/Actuators
AS-Interface Bus
Maximum I/O points when using AS-Interface master module
AS-Interface Master Module
1 module
Maximum Slaves
62 slaves
Maximum I/O Points
434 (248 inputs / 186 outputs)
Maximum Communication Distance
Without repeater:
100m
With 2 repeaters:
300m
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...