Optional Range
When Optional range is selected as an analog input data type, the analog input is linearly converted into digital data in the
range between the minimum and maximum values designated in the Configure Parameters dialog box.
Celsius and Fahrenheit
When Celsius or Fahrenheit is selected as an analog input data type, the analog input data range depends on the analog
input signal type, scale value, and the type of the analog input module, FC4A-L03AP1, FC4A-J4CN1, and FC4A-J8AT1.
•
FC4A-L03AP1
•
FC4A-J4CN1
•
FC4A-J8AT1
Resistance
When Resistance is selected as an analog input data type, the analog input is linearly converted into digital data in the
range described in the table below. This option is available only when NTC or PTC type thermistor is selected for the
FC4A-J8AT1.
•
FC4A-J8AT1
Type No.
FC4A-L03A1
FC4A-L03AP1
FC4A-J2A1
FC4A-J4CN1
FC4A-J8C1
FC4A-J8AT1
Analog Input Data
Analog input data minimum value to maximum value (–32768 to 32767)
Analog Input Signal Type
Celsius
Fahrenheit
Temperature (°C)
Analog Input Data
Temperature (°F)
Analog Input Data
Type K thermocouple
0 to 1300
0 to 13000
32 to 2372
320 to 23720
Type J thermocouple
0 to 1200
0 to 12000
32 to 2192
320 to 21920
Type T thermocouple
0 to 400
0 to 4000
32 to 752
320 to 7520
Pt100 resistance thermometer
–100.0 to 500.0
–1000 to 5000
–148.0 to 932.0
–1480 to 9320
Analog Input
Signal Type
Scale
Celsius
Fahrenheit
Temperature (°C)
Analog Input Data
Temperature (°F)
Analog Input Data
Type K thermocouple
×
1
0 to 1300
0 to 1300
32 to 2372
32 to 2372
×
10
0.0 to 1300.0
0 to 13000
32.0 to 2372.0
320 to 23720
Type J thermocouple
×
1
0 to 1200
0 to 1200
32 to 2192
32 to 2192
×
10
0.0 to 1200.0
0 to 12000
32.0 to 2192.0
320 to 21920
Type T thermocouple
×
1
0 to 400
0 to 400
32 to 752
32 to 752
×
10
0.0 to 400.0
0 to 4000
32.0 to 752.0
320 to 7520
Pt100, Pt1000
resistance
thermometer
×
1
–100 to 500
–100 to 500
–148 to 932
–148 to 932
×
10
–100.0 to 500.0
–1000 to 5000
–148.0 to 932.0
–1480 to 9320
×
100
0.00 to 500.00
–100.00 to 327.67
0 to 50000
–10000 to 32767
0.00 to 655.35
–148.00 to 327.67
0 to 65535
–14800 to 32767
Ni100, Ni1000
resistance
thermometer
×
1
–60 to 180
–60 to 180
–76 to 356
–76 to 356
×
10
–60.0 to 180.0
–600 to 1800
–76.0 to 356.0
–760 to 3560
×
100
–60.00 to 180.00
–6000 to 18000
0.00 to 356.00
–76.00 to 327.67
0 to 35600
–7600 to 32767
Analog Input
Signal Type
Scale
Celsius
Fahrenheit
Temperature (°C)
Analog Input Data
Temperature (°F)
Analog Input Data
NTC thermistor
×
1
–50 to 150
–50 to 150
–58 to 302
–58 to 302
×
10
–50.0 to 150.0
–500 to 1500
–58.0 to 302.0
–580 to 3020
Analog Input Signal Type
Resistance
Resistance (
Ω
)
Analog Input Data
NTC/PTC thermistor
0 to 100000
0 to 10000
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...