IDEAL Vanguard L 1100 Installation And Servicing Download Page 5

5

Vanguard L  - 

Installation & Servicing 

GENERAL

fLuE INSTALLATIoN

ImPoRTANT

It is the responsibility of the installer to ensure that products of 

combustion discharging from the terminal cannot re-enter the 

building or any other adjacent building.

Fan dilution systems may be incorporated into the flue system.  

However, ventilation must take into account the additional air 

requirement of the boiler house and interlocking must be provided 

to ensure adequate air flow is attained before burner operation 

proceeds.

The flue must be installed in accordance with the appropriate 

standards listed on page 4.

WATER cIRcuLATIoN SySTEm

The system pump MUST be connected to the boiler.

The boiler must NOT be used for direct hot water supply.  The 

calorifier MUST be of the indirect type.

The appliances are NOT suitable for gravity central heating nor 

are they suitable for the provision of gravity domestic hot water.

The calorifier and ancillary pipework, not forming part of the 

useful heating surface, should be lagged to prevent heat loss and 

any possible freezing - particularly where pipes run through roof 

spaces and ventilated underfloor spaces.

The boiler must be vented.

Draining taps MUST be located in accessible positions, which 

permit the draining of the whole system - including the boiler 

and hot water storage vessel.  They should be at least 1/2" BSP 

nominal size and be in accordance with BS. 2879.

The central heating system should be in accordance with the 

relevant standards listed on page 4.

Due to the nature of the boiler the heat stored at the point of 

shutdown of the burner must be dissipated in order to avoid 

overheating.  In order to allow pump operation after burner 

shutdown the boiler control box incorporates a pump overrun 

facility.  In order to make use of this, the pump must be supplied 

from the terminals inside the boiler.  Note: for pumps requiring 

greater than 1.0amp current or using 3 phase they must be 

connected via a relay.

WATER TREATmENT foR HoT WATER AND 

HEATING BoILERS

There is a basic need to treat the water contained in all heating 

and indirect water systems, particularly open vented systems.  

It is assumed, incorrectly, that because boilers are operating 

in conjunction with what is apparently a closed circuit an open 

vented system will not, under normal circumstances, allow 

damage or loss of efficiency due to hardness salts and corrosion 

once the initial charge of water has been heated up a few times.

1mm of lime reduces the heat transfer from metal to water by 

10%.

In practice the deposition of these salts is liable to cause noises 

from the boiler body or even premature boiler failure.  Corrosion 

and the formation of black iron oxide sludge will ultimately result in 

premature radiator failure.

Open vented systems are not completely sealed from the 

atmosphere if proper venting and expansion of system water is to 

be achieved.  The same tank is used to fill the system with water 

and it is through the cold feed pipe that system water expands 

into the tank when the boiler passes heat into the system.

Conversely, when the system cools, water previously expelled is 

drawn back from the tank into the system together with a quantity 

of dissolved oxygen.

Even if leakage from the heating and hot water system is 

eliminated there will be evaporation losses from the surface of the 

tank which, depending upon ambient temperature, may be high 

enough to evaporate a large portion of the system water capacity 

over a full heating season.

There will always be corrosion within a heating or hot water 

system to a greater or lesser degree, irrespective of water 

characteristics, unless the initial fill water from the mains is 

treated.  Even the water in closed systems will promote corrosion 

unless treated.  For the reason stated, 

Ideal

 strongly recommend 

that when necessary the systems is thoroughly cleaned, prior 

to the use of stable inhibitor, which does not require continual 

topping up to combat the effects of hardness salts and corrosion 

on the heat exchangers of the boiler and associated systems.

Ideal

 advise contact directly with specialists on water treatment 

such as:
Betz Dearborn Ltd 

or 

Fernox Manufacturing Co. 

Ltd.

Widnes,  

 

Tandem House, Marlowe Way,

Cheshire, 

 

 

Croydon, Surrey, CRO 4XS

Tel: 0151 424 5351 

 

Tel: 0870 601 5000

ELEcTRIcAL SuPPLy

WARNING

 

This appliance must be earthed.  

control Panel:

A 230V - 50Hz.  Fused at 4 amps.
Wiring external to the appliance MUST be in accordance with 

the current I.E.E. (BS7671) Wiring Regulations and any local 

regulations which apply.

Burner and Pump:

These may be 1ph or 3ph.  Refer to manufacturer's instructions.

The point of connection to the mains should be readily accessible 

and adjacent to the boiler.

LocATIoN of THE BoILER

The boiler must stand on a non-combustible floor (i.e. concrete 

or brick) which must be flat, level and of a suitable load bearing 

capacity to support the weight of the boiler (when filled with water) 

and any ancillary equipment.

If the boiler is mounted on a plinth then the dimensions must 

exceed the plan area of the boiler by at least 75mm on each side.

The boiler must not be fitted outside.

Summary of Contents for Vanguard L 1100

Page 1: ...you can be assured conform to the safety and performance specification that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy o...

Page 2: ...60 90 60 90 60 90 Safety thermostat setting C 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 High low setting C 54 84 54 84 54 84 54 84 54 84 54 84 54 84 54 84 54 84 54 84 54...

Page 3: ...ficiency operation ease of maintenance fuel flexibility and low emissions Suitable for oil or gas operation the Vanguard L range is supplied in a choice of 18 standard models rated in outputs from 130...

Page 4: ...ACENT TO THE BOILER EN 304 Test code for heating boilers for atomizing oil burners 73 23 EEC Low voltage directive Relevant standard is EN60335 1 89336 EEC Electromagnetic Compatibility Directive Rele...

Page 5: ...lime reduces the heat transfer from metal to water by 10 In practice the deposition of these salts is liable to cause noises from the boiler body or even premature boiler failure Corrosion and the fo...

Page 6: ...170 630 T1 Flow connection T2 Return connection T3 Safety valve and expansion connection T4 Drain connection T5 Flue connection T6 Burner connection Boiler Size 170 240 290 340 420 510 630 Dimension A...

Page 7: ...E T1 N O P T3 T2 I H T6 T4 T5 T1 T3 T2 1 2 3 4 41 11 16 17 30 24 12 13 21 14 15 22 23 40 van8099 Boiler Size 760 870 970 Dimension A mm 1122 1122 1122 Dimension B mm 1605 1800 1995 Dimension C mm 1432...

Page 8: ...dimensions for boiler room access requirements Boiler Size 1100 1320 1570 1850 2200 2650 3000 3500 Dimension A mm 1352 1352 1462 1462 1622 1622 1720 1970 Dimension B mm 1952 2292 2282 2652 2692 3014 3...

Page 9: ...oned so that there is enough space available to allow the following Access around the boiler for servicing Space to open the boiler front door Space to access the burner Recommended minimum clearances...

Page 10: ...of the system 4 The boiler is at the highest point of the system Systems designed to rise above the flow connections will of course automatically require a minimum static head higher than shown 5 The...

Page 11: ...g Other British Standards applicable to commercial sealed systems are BS6880 Part 2 BS 1212 BS 6281 Part 1 BS 6282 Part 1 BS 6283 Part 4 8 Ventilation Safe efficient and trouble free operation of conv...

Page 12: ...shall be inclined upwards at 45 9 Fluing Flue Size Refer to applicable regulations while determining the size and height of the flue Please note that Vanguard L boilers have pressurised and sealed com...

Page 13: ...ght Jacket 1 Upper Rear Central Left Jacket 1 Support for the Upper Jacket 1 Body Insulation 1 1 1 1 1 1 Front Insulation 1 1 1 1 1 1 Rear Insulation 1 1 1 1 1 1 Central Body Insulation 1 1 Rear Side...

Page 14: ...M16 8 8 8 8 8 8 8 16 16 16 16 16 16 16 16 16 16 16 M12x60 M12x60 M16x70 M16x70 M16x70 M16x70 M16x70 M16x70 M16x70 M16x70 M20x80 M20x80 M20x80 M20x80 M20x80 M20x80 M120x80 M20x80 1 1 1 1 1 1 1 1 1 1 1...

Page 15: ...nels 3 and 4 D Fit the rear insulation 6 fix the rear lower and upper retaining strips 7 and 8 with the self tapping screws Fit the plastic cable clamps 9 to the upper rear panel 8 E Fit the Ideal bad...

Page 16: ...3 4 van8103 16 Position of thermometer thermostat sensor in the bulb holder Vanguard L 170 to 970 LEGEND 1 Thermometer bulb 2 Operation thermostat bulb 3 Safety thermostat bulb 4 Minimum temp thermost...

Page 17: ...r insulation 7 fix the rear lower panels 9 with pins and springs and the upper panel 10 with the self tapping screws 8 Fit the plastic cable clamps 11 to the upper rear panel 10 E Fit the Ideal badge...

Page 18: ...the plastic cable clamps 8 to it E Fit the Ideal badge to the front edge of the front top panel 9 and secure with the rubber fixings F Fit the control panel to front top panel 9 Remove the upper shell...

Page 19: ...front edge of the front top panel 8 and secure with the rubber fixings F Fit the control panel to front top panel 8 Remove the upper shell of the control panel and insert the capillaries of thermomete...

Page 20: ...ok them to the screws fitted to the upper square tube To determine which one of the front side panels is the left or the right ensure that the cable clamp plates 7 are positioned facing toward the fro...

Page 21: ...ostat 3 Safety thermostat 4 Minimum thermostat Ensure that the sensors are inserted to the bottom of the bulb holder and then secure them with the retaining clip 5 In case some other thermostat is nec...

Page 22: ...mber can be achieved through adjustment of the screws 23 Door Assembly Vanguard L 170 to 630 Models The combustion chamber door is fitted with four fixing points two on the left hand side which are no...

Page 23: ...when reversing the door the bushing 9 nut 10 and washer 11 will have to be moved as shown below details 1 and 3 for hinge side details 2 and 4 for hinge side Door Adjustment 1 Vertical door adjustmen...

Page 24: ...be and the hole in the door insulation Gas Supply The gas supply MUST be sized in accordance with British Gas recommendations and be prefabricated in compliance with CP 331 Pt 1 and any Local Gas Boar...

Page 25: ...ur meter not supplied High low regulating thermostat Minimum thermostat Safety thermostat with manual reset N B With three phase the motor must be connected directly in this case the instrument panel...

Page 26: ...tting Live on this lead hence on T2 allows burner to fire on low fire in a 2 stage burner No 10 S3 Burner lockout indicator Feeds signal from lockout terminal on burner control box to a remote lock ou...

Page 27: ...FF Switch illuminated Position I ON Position OFF 12 Burner Switch Position I ON Position OFF 13 Pump Switch Position I I ON Position OFF 21 Boiler ON OFF High Low Thermostat High fire 54 C 84 C low fi...

Page 28: ...tors will be placed inside the relevant smoke pipes at a distance from the front tube plate as shown in the picture on the right When using the boiler at minimum output the smoke temperature will not...

Page 29: ...and drain down to complete the flushing process c Refill and vent the system clear all air locks and again check for water soundness d Balance the system 3 Finally set the controls to the User s requ...

Page 30: ...freezing Otherwise drain the system completely 39 Safety For boilers with gas burners It is the law that any service work must be carried out by a Gas Safe Registered Engineer WARNING Always turn off...

Page 31: ...es 4 Close off the fuel supply to the burner 5 Ensure that the boiler has been cooled to ambient temperature 6 Isolate the mains supply to the boiler and burner 7 Open the combustion chamber door afte...

Page 32: ...Technical Helpline 01482 498 376 www idealheating com Ideal Boilers P O Box 103 National Ave Kingston upon Hull HU5 4JN Telephone 01482 492 251 Fax 01482 448 858 Registration No London 322 137 Ideal...

Reviews: