background image

2

#61-154
#61-155

Introduction

The SureTest

®

family of circuit analyzers were designed to 

troubleshoot branch circuits quickly, easily and accurately.
They have a patented technology that allows them to test
branch circuits under a full load condition to identify 
hidden problems behind the wall that will not be
found with traditional testing methods.

Product Features

• True RMS
• Measures voltage drop under 12, 15 and 20-amp load
• Line voltage
• Peak voltage
• Frequency
• Ground impedance
• Hot and neutral conductor impedances
• Ground-neutral voltage
• Identifies proper wiring in 3-wire receptacles
• Identifies false (bootleg) grounds
• Verifies dedicated circuits (with 61-176 adapter)
• Tests GFCIs for proper operation
• Tests AFCI’s for proper operation (61-155)
• Includes carrying case 
• Includes 1-ft. extension cord

General Operation

The SureTest

®

Circuit Analyzer, #61-154 and SureTest® Circuit Analzer,

#61-155 take only seconds to test each outlet and circuit under a full load.
They check for various wiring conditions, including: correct wiring, polarity
reversal, hot/ground reversal and no ground.  A simple programming menu
gives access to measurements of line voltage, voltage drop under a full load
condition, ground-neutral voltage and line impedances.  The ground fault
circuit interrupter (GFCI) test is performed separately and will disrupt the
electrical supply if a functional GFCI is present

The SureTest

®

w/AFCI, #61-155, will also test arc fault circuit interrupter

(AFCI) test to ensure that AFCI breakers protecting the circuit have been
installed correctly and are operating properly.  This test is performed sepa-
rately in accordance with UL1436, and will disrupt the electrical supply if a
functional AFCI is present.

For proper troubleshooting of a branch circuit, insert the SureTest into the fur-
thest receptacle from the panel.  Any discrepancies from a normal reading dur-
ing a measurement indicate that a problem has been detected in the circuit.
Allow at least 20 seconds between insertions.  Repeatedly inserting the SueTest
into a receptacle will cause the unit to heat up which may affect the accuracies.

General Specifications

Case construction:

ABS UL 94 V/0/5VA rated

Operating Range:

108 to 132 Volts

Display:

97x32 Pixel Graphics Display with backlight

Dimensions:

6.5” x 3” x 1”

Weight:

9.4oz

Environmental Specifications

Operating Temp.:

0° C to 50° C

Storage Temp.:

0° C to 50° C

Humidity:

<80% RH

Altitude:

2000m (6667 ft.)

Safety:

Designed to IEC 1010-1 UL3111

Input Rating:

150VAC Category III

Overvoltage Category:

Cat III: Distribution level mains, fixed installations
Cat II: Local level mains, appliances, portable 
equipment
Cat I: Signal level, special equipment or parts of 
equipment, telecommunications, electronics

Pollution Degree 2:

Do not operate in environments where conductive 
pollutants may be present

WARNING:

Do not use on outputs from UPS systems, light 

dimmers or square wave generating equipment.

SureTest

®

Circuit Analyzer and 

SureTest

®

w/AFCI Instructions

Sold by:

http://www.TWAcomm.com

Toll Free: (877) 892-2666

Summary of Contents for SureTest 61-154

Page 1: ...155 will also test arc fault circuit interrupter AFCI test to ensure that AFCI breakers protecting the circuit have been installed correctly and are operating properly This test is performed sepa rat...

Page 2: ...tes that the unit is in a sub menu This will be displayed just under the menu grid on the unit s display Using the menu grid and menu level indication will help the user step through the menu as indic...

Page 3: ...icon It consists of a grid and either an up or down arrow The grid on the display has four regions that correspond to each of the menu selections as listed on the face of the unit The appropriate regi...

Page 4: ...the circuit To determine what may be causing the problem turn off the loads on the circuit and re check If the test results do not change than the problem may be within the circuit If the test result...

Page 5: ...voltage on the branch load on the circuit drop circuit Undersized wire Check code for length of run requirements and re wire if necessary High resistance Locate high connection within resistance the c...

Page 6: ...ry gauge wire High resistance Locate high 0 01 connection within resistance foot of 10 the circuit or at connection device gauge wire the panel and repair replace Neutral 0 48 High Too much load Redis...

Page 7: ...the GFCI may be at the receptacle or at the panel To activate the GFCI test press the GFCI button GFCI from anywhere with in the measurement menu The actual current being bled from hot to neutral will...

Page 8: ...he receptacle and make a note of the results See the section on Line Impedance Testing for details Remove the SureTest and plug it into the isolated ground adapter Attach the alligator clip to the cen...

Page 9: ...ire is sized per code and measure the current on the branch circuit The reading may not decrease at all from the last receptacle to the first This would indicate that the problem could be at the first...

Page 10: ...ES INC will at its option replace or repair the defective unit subject to verification of the defect or malfunction This warranty does not apply to defects resulting from abuse neglect accident unauth...

Reviews: