OVERHEAT THERMOSTAT

Each module is fitted with an overheat thermostat.  If the overheat 

thermostat is fitted the MAINS ON and OVERHEAT lights will be 

illuminated.
To reset the overheat thermostat press in the green button 

labelled 'Overheat Reset'.
Provided that the temperature at the sensing point has fallen 

sufficiently, the module will automatically begin its start sequence 

and the burner will light.
Frequent tripping of the overheat thermostat should be 

investigated by a CORGI registered installer.

MODULE CONTROL THERMOSTAT

All Models

The module control thermostat has been set by the boiler 

Commissioning Engineer to give the correct sequence of module 

operation.

IMPORTANT

The module thermostat should not therefore be altered by the 

User.

TO SHUT DOWN A MULTI-MODULE 

BOILER

1.  For short periods:

Turn off the electricity supply to the boiler.

2.  For longer periods:

Turn OFF the mains electricity supply.
Turn OFF all module gas service taps.
Turn OFF the main inlet gas tap.

Turn water and all system controls to OFF.

FROST WARNING

If frost is likely during a short absence, leave the boiler running.  
For longer periods, unless the controls include a frost thermostat, 

the system should be drained.

MAINTENANCE

IMPORTANT

In order to ensure safety and reliable operation of 

Super Plus

 

boilers it is essential that regular maintenance be carried out by 

competent staff who have received instruction in maintenance, fault 

finding and commissioning procedures for this boiler series.

IMPORTANT
1. 

Towels etc. MUST NOT be draped over the boiler casing.

2. 

The User MUST ensure that the boiler house is maintained in a 

clean and tidy condition, and that NO loose items can fall on to 

the boiler.

  The boiler should NOT be operated during the course of 

building, painting, piping or lagging work etc., in the boiler 

house.

  When such work is in progress, the modules should be covered 

by means of clean dust sheets.

3. 

The passage of combustion and ventilation air via air tracks to 

the boiler must NOT be restricted.

4. 

The boiler house MUST NOT be used for storage purposes.

5. 

Check that the condensate drain is not blocked.

ESCAPE OF GAS

Should a gas leak be suspected contact your Local Gas Region 

without delay.

DO NOT search with a NAKED FLAME.

2  WATER TREATMENT

The 

Super Plus 

incorporates an aluminium alloy heat 

exchanger.  As part of the installation the central heating system 

should be thoroughly flushed with appropriate water treatment in 

order to comply with BS7593:1992.

UNDER 

NO 

CIRCUMSTANCES SHOULD THE BOILER BE 

FIRED BEFORE THE SYSTEM HAS BEEN THOROUGHLY 

FLUSHED.
Caradon Ideal Limited 

recommend only the use of Fernox, GE 

Betz Sentinel or Salamander water treatment products, which 

must be used in accordance with the manufacturers instructions.  

For further information contact:

Fernox, Cookson Electronics, Forsyth Road, Sheerwater,

Woking, Surrey, GU21 5RZ

Tel: +44 (0) 1799 550811

or

GE Betz, Sentinel Division, Foundry Lane, Widnes, 

Cheshire, WA8 8UD.

Tel: +44 (0) 151 420 9563

or

Salamander (Eng) Ltd., Reddicap Trading Estate, Sutton 

Coldfield, West Midlands, B75 7BY

Tel: +44 (0) 121 378 0952

IMPORTANT:

 ANY OTHER TREATMENT FOR THIS PRODUCT 

WILL RENDER THE GUARANTEE OF CARADON IDEAL 

LIMITED 

INVALID

.

Notes.
1. 

If an inhibitor is used, and in hard water areas where 

treatment to prevent lime deposits is necessary, it is most 

important that the water treatment MUST be maintained at 

the correct concentrations recommended by the treatment 

manufacturer.

  Persons responsible for the continued operation of this boiler 

should be made aware of this requirement.

  If the boiler is installed in an existing system then any 

unsuitable water additives MUST be thoroughly drained.

2. 

Artificially softened water must not be used in the system, 

under any circumstances.

3.

  In all systems the fitting of a filter to the return pipework, 

in order to prevent debris reaching the heat exchanger, is 

essential.

Summary of Contents for SUPER PLUS 200/S

Page 1: ... parts that you can be assured conform to the safety and performance specification that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature for specification and maintenance practices visit our website www idealcommercialboilers com where you can download the relevant information in PDF format ...

Page 2: ... position in the switching sequence either the fan will run on for a further 35 seconds or the fan will stop for a period of up to 35 seconds then restart and run for a further 35 seconds The operation is part of the pre purge safety feature of the Super Plus boiler c At the end of this period the gas valve will open and the spark generator will be energised The burner will light and can be seen t...

Page 3: ...use When such work is in progress the modules should be covered by means of clean dust sheets 3 The passage of combustion and ventilation air via air tracks to the boiler must NOT be restricted 4 The boiler house MUST NOT be used for storage purposes 5 Check that the condensate drain is not blocked ESCAPE OF GAS Should a gas leak be suspected contact your Local Gas Region without delay DO NOT sear...

Page 4: ...32 Ideal is a trademark of Ideal Boilers Registered Office Ideal Boilers Ltd PO Box 103 National Avenue Kingston Upon Hull HU5 4JN Tel 01482 492251 Fax 01482 448858 Registration No London 322 137 Ideal Technical Helpline 01482 498376 www idealcommercialboilers com Ideal Boilers Ltd pursues a policy of continuing improvement in the design and performance of its products The right is therefore reser...

Reviews: