FAULT FINDING
50
Mini
--- Installation & Servicing
Are LED 1 and LED 3
flashing with LED 2
on, plus LED 4 on the
facia on?
Is there >17mbar at
the gas valve inlet?
Rectify gas supply
fault.
Press reset button.
Is there 230V across
the Black and Blue
gas valve connection
during ignition?
Is there
230V at
Black and
Blue at gas
valve
harness
connector
on PCB
#2?
Is there
230V at pin 101
Brown on
PCB
connecting
harness at
PCB #2?
Is there
230V at pin 11
Brown on
PCB
connecting
harness at
PCB #1?
Replace
faulty PCB
#1.
Repair or replace faulty wiring
Is fuse continuity O.K on PCB #2?
Replace faulty PCB #2.
Replace
fuse.
Repair or
replace
faulty wiring
Is there a burner
pressure during
ignition period?
Has the main
overheat thermostat
operated?
(Check continuity)
Is there continuity of
over heat thermostat
wiring at PCB
connection?
Repair or replace
damaged wiring.
Replace faulty gas
valve.
Allow boiler to cool
and press re---set.
Is there ignition at the
burner?
Is a spark
visible at the
burner during
ignition?
Are the
ignition leads
disconnected
or damaged
and sparking
to earth?
Are the
ignition leads
correctly
connected to
PCB #2?
Rectify
faulty
connection.
Replace
faulty PCB #2
Replace
faulty
electrode
assy. Make
connection.
Adjust ignition burner
pressure.
Continued from page 49
of fault finding
Continued on page 51 of
fault finding
Ensure the ignition electrode position and spark gaps are correct.
Rectify or replace. Refer to frame 43.
Is the ignition burner
pressure correct? Refer
to frame 29.
no
yes
yes
yes
yes
yes
yes
no
no
no
no
no
no
yes
yes
yes
no
yes
yes
yes
no
no
no
no
no
no
no
yes
yes
yes
no
Continued on
page 52 of
fault finding
FA
U
LT
F
IN
D
IN
G