15
LOGIC HIU
50 DIRECT MEDIUM TEMP
Maximum working pressure:
10 bar
Maximum temperature
85°C
Max. Percentage of glycol
30%
Max. Recommended primary
circuit flow rate
1.2 m
³
/h
PRIMARY PERFORMANCE
Heat Interface Unit MT
Primary ball valve set
Central heating flow & return valves
DHW inlet and outlet connection valves
Differential pressure control (DPC)
UIN
PRODUCT NAME
METERING OPTIONS
211095
Logic HIU Direct MT
HIU only, meter not
included
211348
Logic HIU Direct MT
Factory fitted, CF Echo 11
MbBus 1
211352
Logic HIU Direct MT
Factory fitted, CF
Ultramaxx V MBus PS
Power supply
230 V (ac)
±
10% 50 Hz
Max. Power consumption
105 W
Protection class
IP 40
Actuator
Stepper 24 V
Probes
NTC 10 k
Ω
ELECTRICAL
Frame
RAL 9010 sprayed steel
Protective shell cover
EPP (Expanded polypropylene)
Components
Brass BS EN 12165 CW617N
Pipes
Stainless steel
Exchanger
Brazed stainless steel
CONSTRUCTION
INCLUDED AS STANDARD
The temperature setting operates on the principle of set
point regulation and can be fixed within application limits.
HEATING
The DHW function takes priority over the heating function
controlled by the DHW priority flow switch.
Set Point DHW temperature
42 to 60°C
Max. Domestic hot water
pressure
10 bar
DHW circuit max. flow rate
18 l/m (0.3 l/s)
Min. flow rate to activate
domestic flow sensor
2.7 l/m
±
0.3
Max. Differential pressure on
domestic water modulating
valve
Δ
p 0.9 bar
Min. Differential pressure on
domestic water modulating
valve
Δ
p 0.35 bar
Nom. DHW heat exchanger
net output
50 kW - Logic HIU 50
Direct MT
DOMESTIC HOT WATER - DHW
INCLUDING OPTIONAL PRE HEAT FUNCTION
Flushing By-pass
CF Echo II
CF Ultramaxx V
ACCESSORIES
Heating Set Point
50 to 75°C
Nom. heating net output
As primary and heating circuit
controls permit
Heating circuit
Maximum pressure rating: 10
bar as primary and heating
circuit
controls permit
Pump
UPS 15/60
Pump bypass setting
0.45 bar
Heating control circuit
VOLT FREE