background image

Exalt

Application Guide

6

7.  A list of 4 Flex Relays are clickable. These are the 

Boiler actions to be edited. 

Fig. 15:  Flex. Relays

•  When selecting Flex Relay 1, the boiler pump ac-

tions are being edited.

•  When selecting Flex Relay 2, the DHW pump ac-

tions are being edited.

•  When selecting Flex Relay 3, the CH2 pump actions 

are being edited.

•  When selecting Flex Relay 5, the CH1 pump actions 

are being edited.

8.  Select the relay to be changed. Choose whether 

the relay will be on or off for any of the following 

calls:

 CH1, CH2, DHW, MIX OPEN, MIX CLOSE, ERROR, 

FLAME.

•  When selecting CH1, the relay is activated at CH1 

demand.

•  When selecting CH2, the relay is activated at CH2 

demand.

•  When selecting DHW, the relay is activated at DHW 

demand.

•  Mix Open is not functional in the Exalt Boilers.

 

•  Mix Close is not functional in the Exalt Boilers.

•  When selecting ERROR, the relay is activated on 

error.

•  When selecting FLAME, the relay is activated when 

appliance is running and a flame signal has been 

detected.

9.  Once the Relay's actions have been selected, scroll 

down and hit enter on the 

Save and Exit

 option at 

the bottom. This relay shown in Fig. 16 is set to turn 

on the pump wired to the boiler pump terminal for 

CH1, CH2 and DHW calls. 

Fig. 16:  Flex. Relay 1 Settings

Fig. 17:  Flex. Relay 1 Save Option

NOTICE

The options will not be saved when quick exiting (hitting the 

house or back arrow at the bottom of the menu).

Summary of Contents for Exalt FSB 110

Page 1: ...sult causing substantial property damage serious injury or death FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT...

Page 2: ...e Option 6 Fig 18 Exalt Solo Near Boiler Piping with Hydraulic Separator 7 Fig 19 Exalt Solo Multiple Temperature Zones with Circulators 8 Fig 20 Exalt Solo Multiple Zones with Circulators 9 Fig 21 Ex...

Page 3: ...the OK button to enter the access code ENTER INSTALLER ACCESS CODE 0 XX Fig 2 Installer Access Code 3 Press the OK button while the CH DHW Settings icon is highlighted Fig 3 CH DHW Settings 4 Press t...

Page 4: ...Call DHW Call B C Out of the box setting CH1 Call CH2 Call DHW Call CH1 Call CH2 Call DHW Call D CH1 Call CH2 Call DHW Call CH1 Call CH2 Call CH1 Call CH2 Call DHW Call E CH1 Call CH2 Call CH2 Call C...

Page 5: ...utton 2 Enter the installer access code 054 by using the LEFT and RIGHT buttons to select a digit and the UP and DOWN buttons to change the digit Press the OK button to enter the access code ENTER INS...

Page 6: ...at CH1 demand When selecting CH2 the relay is activated at CH2 demand When selecting DHW the relay is activated at DHW demand Mix Open is not functional in the Exalt Boilers Mix Close is not function...

Page 7: ...Exalt Application Guide 7 3 Exalt Solo Piping Diagrams Fig 18 Exalt Solo Near Boiler Piping with Hydraulic Separator...

Page 8: ...F OFF CH2 CH2 ON ON OFF OFF ON ON OFF OFF DHW DHW ON ON OFF OFF OFF OFF ON ON Note the boiler is set up in this configuration out of the box Fig 19 Exalt Solo Multiple Temperature Zones with Circulato...

Page 9: ...OFF OFF OFF CH2 CH2 ON ON OFF OFF ON ON OFF OFF DHW DHW ON ON OFF OFF OFF OFF ON ON Note the boiler is set up in this configuration out of the box Fig 20 Exalt Solo Multiple Zones with Circulators NOT...

Page 10: ...Pump CH2 Pump CH2 Pump DHW Pump DHW Pump CH1 CH1 ON ON ON ON OFF OFF OFF OFF CH2 CH2 ON ON OFF OFF ON ON OFF OFF DHW DHW ON ON OFF OFF OFF OFF ON ON Note the boiler is set up in this configuration out...

Page 11: ...FF OFF OFF OFF CH2 CH2 ON ON OFF OFF ON ON OFF OFF DHW DHW ON ON OFF OFF OFF OFF ON ON Note the boiler is set up in this configuration out of the box Fig 22 Exalt Solo Single Zone with Circulator NOTI...

Page 12: ...Boiler Pump CH1 Pump CH1 Pump CH2 Pump CH2 Pump DHW Pump DHW Pump CH1 CH1 ON ON ON ON OFF OFF OFF OFF CH2 CH2 ON ON ON ON OFF OFF OFF OFF DHW DHW ON ON OFF OFF OFF OFF ON ON Note the boiler pump sett...

Page 13: ...Exalt Application Guide 13 Fig 24 Exalt Solo Cascade Layout...

Page 14: ...Exalt Application Guide 14 4 Exalt Combi Piping Diagrams Fig 25 Exalt Combi Near Boiler Piping with Hydraulic Separator...

Page 15: ...OFF OFF OFF CH2 CH2 ON ON OFF OFF ON ON OFF OFF DHW DHW ON ON OFF OFF OFF OFF ON ON Note the boiler is set up in this configuration out of the box Fig 26 Exalt Combi Multiple Zones with Circulators NO...

Page 16: ...F OFF OFF OFF CH2 CH2 ON ON OFF OFF ON ON OFF OFF DHW DHW ON ON OFF OFF OFF OFF ON ON Note the boiler is set up in this configuration out of the box Fig 27 Exalt Combi Single Zones with Circulator NOT...

Page 17: ...F OFF CH2 CH2 ON ON OFF OFF ON ON OFF OFF DHW DHW ON ON OFF OFF OFF OFF ON ON Note the boiler is set up in this configuration out of the box Fig 28 Exalt Combi Multiple Temperature Zones with Circulat...

Page 18: ...er Pump CH1 Pump CH1 Pump CH2 Pump CH2 Pump DHW Pump DHW Pump CH1 CH1 ON ON ON ON OFF OFF OFF OFF CH2 CH2 ON ON ON ON OFF OFF OFF OFF DHW DHW ON ON OFF OFF OFF OFF ON ON Note the boiler pump settings...

Page 19: ...CH2 Pump CH2 Pump DHW Pump DHW Pump CH1 CH1 ON ON ON ON OFF OFF OFF OFF CH2 CH2 ON ON OFF OFF ON ON OFF OFF DHW DHW ON ON OFF OFF OFF OFF ON ON Note the boiler is set up in this configuration out of...

Page 20: ...Ideal 1240 Forest Parkway Suite 100 West Deptford NJ 08066 Tel 800 411 9999 Fax 856 228 3584 E mail info idealusa com...

Reviews: