TroublesHooTing
If for any reason your Ideal Solar EC 1 Controller does not seem to be operating, check the fault finding chart below before
contacting a Solar Qualified Engineer.
WARNING. DO NOT OPEN THE HOUSING
secondary condition:
possible cause:
The controller’s display is blank
No power supply, check fuse and electric mains.
controller shows no function
secondary condition:
possible cause:
Pump symbol does not rotate;
No fault, controller deactivated the pump because
“max“ flashes in the storage symbol
maximum storing temperature has been reached.
Pump symbol does not rotate;
No fault, controller has deactivated the pump because the
Steam symbol flashes on the collector symbol.
collector maximum temperature (130ºC) has been exceeded.
Pump symbol rotates in the display.
Pump’s connecting line is not connected, interrupted or fuse in
the controller is burnt-out (replacement fuses provided in the
housing). Only use fuses of type 250V 4A MT.*
Pump symbol does not rotate;
There is a sensor fault (short circuit or interruption); check the
Backlight display flashes red and green alternately;
sensor supply lines and its connect connection on the
one of the T1/T2 temperature displays a sensor fault.
controller.*
The solar circuit pump connected to the controller does not run, although it
’
s switch on conditions are
met (sun in the display)
Display showing a flashing “SYS”
sys
stands for
system error
. That means in spite of the pump running there is a difference in temperature of more than 80
Kelvin measured between collector and storage tank. The reason for such a huge temperature difference could be a damaged
or faulty connected pump, a closed valve or air in the solar circuit. As air inside the piping can’t be overcome by a conventional
pump, circulation of the solar circuit is stopped. Check your solar-system for these sources of error to avoid damages.*
You can quit the error message afterwards by pressing any key.
If the trouble shooting does not solve the problem then contact your local Solar qualified Engineer.
* Contact a Solar qualified engineer.