Classic
LXRS, RS Propane
-
User's
2
3.
Ensure that the gas inlet cock (E) is OPEN.
4.
Ensure that the boiler thermostat knob (C) is in the OFF (0)
position.
5.
Turn the gas control knob (A) to the RIGHT until resistance is
felt, then release it. WAIT FOR 3 MINUTES
6.
Push in the gas control knob (A) and hold it depressed. Push
in and release the igniter button (D) repeatedly until the pilot
flame can be seen through the sightglass (B). When the pilot
has lit, continue to press in the gas control knob for a further
15 seconds.
7.
Should the pilot go out at this or any other stage turn the gas
control knob (A) to the RIGHT.
WAIT FOR 3 MINUTES then repeat instruction 6, but wait
for longer than 15 seconds before releasing the gas control
knob (A).
8.
Switch ON the electricity supply to the boiler. Check that all
external controls, e.g. room thermostat etc., are ON.
9.
Turn the boiler thermostat knob (C) to position 6 and the
boiler will light. Set the boiler thermostat to the desired
position.
10. Deluxe Model (LX)
- Lower the glass fascia after pushing in
the sliding catch.
Standard Model
- Close the controls access door.
In
winter conditions
, i.e. central heating and domestic hot water,
the thermostat should be set at position '5' or '6'.
For
summer conditions
, i.e. domestic hot water only, the
thermostat should be set at position '3'.
These settings, however, are offered for general guidance only
and other settings may be found preferable, dependent upon the
type of system installed or as recommended by the installer.
Approx. flow temperatures for the boiler thermostat settings are:
Knob Setting
Flow Temperature
°C
°F
1
56
133
2
61
142
3
66
152
4
72
161
5
77
170
6
82
180
Gas Safety (installation and use) Regulations,
1994, amendments 1996 or rules in force.
It is law that
all
gas appliances are installed by a CORGI registered
installer (identified by ) in accordance with the above regulations.
Failure to install appliances correctly could lead to prosecution. It
is in your own interest, and that of safety, to ensure the law is
complied with.
It is essential that the instructions in this booklet
are strictly followed, for safe and economical
operation of the boiler.
ELECTRICITY SUPPLY
This appliance must be efficiently earthed.
This appliance requires 230 V ~ 50 Hz.
This appliance must be connected to the supply via a double pole
switch, fused at 3 Amps, having a 3mm (
1/8
") contact separation
in both poles, serving only the boiler and system controls.
MINIMUM CLEARANCES
The minimum clearances given below MUST be complied with in
order to maintain the safe running of the boiler and to facilitate
servicing.
Above the boiler
100 mm
(4")
At each side of the boiler
5 mm
(
1/4
")
Underneath the boiler
100 mm
(4")
In front of the boiler
450 mm
(17
3 /4
")
IMPORTANT NOTES
a.
THIS APPLIANCE MUST NOT BE OPERATED WITHOUT THE
CASING CORRECTLY FITTED AND FORMING AN ADEQUATE SEAL.
b.
If the boiler is installed in a compartment then the compartment
MUST NOT be used for storage purposes.
c.
The ventilation provided for the boiler during installation MUST
NOT be blocked and a check should be made periodically that
the ventilation areas are free from any obstruction.
d.
If it is known or suspected that a fault exists on the boiler then
it MUST NOT be used until the fault has been corrected by a
CORGI registered installer.
TO LIGHT THE BOILER.
Refer to Frame 1
1.
C
HECK
THAT
THE
ELECTRICITY
SUPPLY
TO
THE
BOILER
IS
OFF
.
2. Deluxe Model (LX)
- Lift the glass fascia and support with the
sliding catch.
Standard Model
- Open the controls access door by hinging
downwards.
THE LOG BOOK SHOULD BE COMPLETED AFTER
EACH SERVICE AND KEPT WITH THESE
INSTRUCTIONS
TO SHUT DOWN THE BOILER
1. For short periods:
Turn the boiler thermostat knob to OFF. When heating is
again required, restore the knob to its original settings.
2. For longer periods:
Turn the boiler thermostat knob to OFF. Turn the gas control
knob (A) to the right until resistance is felt then release it to
extinguish the pilot burner. Switch the electricity supply to OFF.